Wiringdiagram(Monitoroutput)
△
! CAUTION
Whenthemonitoroutputisnotbeingused,preventitfromtouchingtheother
wiresasthiscancauseamalfunction.
Analogueoutput・Voltagetype
(ITV※0※※-※1)
Analogueoutput・Current(sink)type
(ITV※0※※-※4)
Onlyuseequipmentwithaminimumload
impedanceof100kΩ.
Onlyuseequipmentwithamaximumload
impedanceof250Ω.
Switchoutput・NPNtype
(ITV※0※※-※2)
Switch・PNPtype
(ITV※0※※-※3)
When a current of approx.150mADC or
more is applied, the over current
circuit is archived, “Er.5” is
displayedandtheoperationstops.
Please use with installing the load
that the output current becomes to
80mADCorless.
Whenacurrentofapprox.150mADCor
more is applied, the over current
circuit is archived, “Er.5” is
displayedandtheoperationstops.
Pleaseusewithinstallingtheloadthat
theoutputcurrentbecomesto80mADCor
less.
Monitoroutputvoltage
1:Brown
3:Blue
2:White
4:Black
○
+
○
-
Monitoroutputcurrent
1:Brown
3:Blue
2:White
4:Black
○
+
○
-
Load
1:
Brown
3:
Blue
2:
White
4:
Black
Load
1:
Brown
3:
Blue
2:
White
4:
Black
―6―