Operation Manual 7 Parameters of LCD
33
Parameter Range Default
HVRT normal vol max(%) 110~120 110
HVRT tolera vol max (%) 120~140 130
Tmax-HVRT normal(ms) 100~20000 10000
Tmax-HVRT tolera(ms) 100~5000 500
Active Islanding Enable/Disable Disable
I leakage-pro(A) 1~8 5
Anti-PID mode Invalid/Suppression/Repair
Invalid (mode disabled)/
Suppression (mode
enabled)
Ins monitor measure time (S) 30/150/300/600 150
Ins monitor protect
threshold(K)
15~100 33
Note: * non-settable
Please refer to the LCD screen for the specific setting ranges of these parameters.