Operation Manual 9 Routine Maintenance
43
Item Method Interval
Save software
data
Read out SolarInfo Logger data;
Save running data, parameters and logs to a disk or
a file;
Check each parameter setting;
Update software
Once a month
System general
running status
and
environment
Check the inverter for visible damages or
deformation;
Check the inverter for any abnormal noise during
running;
Check each parameter of the inverter during
normal operation;
Check the principal components;
Check if the enclosure temperature is normal with
the thermal imager;
Check the air inlet and outlet;
Check the ambient humidity, dust and air inlet
filter;
Notice! Check the air inlet and outlet. The equipment
may be damaged by overheating.
Every six months
System cleaning
Check whether the circuit board and the
component are clean;
Check the temperature and dust of the heat-sink.
Use vacuum cleaner to clean the module if necessary;
Replace the air filter.
From every six
months to annually
depending on the
dust deposits.
Power circuit
connection
Check whether the power cable connections are
loose. Retighten them with the torque specified in
the manual if necessary;
Check if the power cables and control cables,
especially the surface in contact with the metal are
damaged;
Check if the wrap belt of the connection terminals
is strip-off.
Six months after
commissioning for
the first time and
then once every six
month to a year
Terminal and
cable
connection
Check whether the screws of the control terminals
are loose. Refasten them with screwdriver if
necessary;
check whether the terminals of the main circuit are
in poor contact and whether the screws are hot;
check if the connection busbar or screws are
discoloring.
Visual check the wiring copper bus or bolt for
discoloration;
Once per year
Fan
maintenance
and
replacement
check if there is crack in the fan blade;
Check if there is abnormal noise during the
running of the fan;
Replace the fan if necessary.
Once per year
Device
maintenance
routine check of the corrosion of the metal
components (once six months)
annually check the contactors (auxiliary switches
and micro-switches) to ensure the optimal operation;
Check the running parameters (Voltage and
insulation especially)
From every six
months to annually
Safety function
Check the emergency stop button and the LCD
stop function;
Simulation shutdown and check the shutdown
signal communication signal;
Check the warning labels and other markings for
damage or unclearness. Replace them if necessary.
From every six
months to annually
Software
maintenance
Optimize software
Check each parameter setting
From every six
months to annually