10 Troubleshooting Operation Manual
48
Fault
F-fault
Possible
reason
The grid frequency is outside the permitted range
Measure
Check grid frequency
Check if the AC cables are securely connected.
Remar
Inverter automatically reconnects to the grid once the grid voltage recovers normal
Fault
Gnd-flt
Possible
reason
Inverter AC side leakage current to the ground exceeds the set value (default: 5A)
Measure
-
Remar
Inverter automatically reconnects to the grid once the leakage current recovers
Fault
Iac-high
Possible
reason
Internal short-circuit or internal components damages
Measure
Check the AC side cable connection and the control circuit board.
Remar
Contact Sungrow
Fault
Temp-flt
Possible
reason
Inverter internal temperature exceeds the permitted value
Measure
Check functionality of fan after the device is voltage-free
Remar
Stop the inverter if this fault occurs 10 times per day
Fault
PM-high
Possible
reason
Module temperature exceeds the permitted value
Measure
Check the module and ventilation after the device is voltage-free
Remar
Stop the inverter if this fault occurs 5 times per day
Fault
L over-temp
Possible
reason
Reactor temperature exceeds the permitted value
Measure
Check the reactor after the device is voltage-free
Remar
-
Fault
PDP-pro
Possible
reason
Internal fault
Measure
Wait 5 minutes for inverter auto-reconnection or disconnect first and then connect
the AC main switch
Contact Sungrow if the fault insists
Remar
Stop the inverter if this fault occurs 5 times per day
Fault
Cntr-flt
Possible
reason
Contactor connected to the gird failure
Measure
Check the contactor after the device is voltage-free
Remar
Stop the inverter if this fault occurs 5 times per day。