| SAVECair control
Alarm name Explanation Do the following
Filter
Time for filter change. Change the filter.
Change filter according to the
instructions in the User Manual.
Details about filter retailers can be
found in Help menu.
Extra controller alarm
Error from external device. Check if external device is connected
properly and cable is not damaged.
Reset overheat protection on
electrical pre-heater. Contact your
installation company or place of
purchase.
External stop
Unit is stopped by external signal. Operation is stopped by digital signal
from external remote device or
signal from building management
system.
Manual fan stop active
Operation stopped, fans are in
manual mode and selected as OFF.
Select another speed of fans (LOW /
NORMAL / HIGH) or AUTO mode in
HMI home screen.
Overheat temperature
Temperature after reheater is too
high.
Active: (Overheat temperature
sensor measures > 55°C)
Returned: (Overheat temperature
sensor measures < 50°C)
Alarm is possible if supply airflow is
too low when the reheater is
switched on.
Check the supply airflow.
Check that intake grille is not
blocked.
Check that shut off damper for
outdoor air is open in operation.
Contact your installation company or
place of purchase.
Low supply air temperature
Supply air temperature is too low.
Active: (Outdoor air temperature
sensor measures < 0°C) AND (Supply
air temperature sensor measures <
5°C)
Returned: (Supply air temperature
sensor measures > 10°C)
Check the heat exchanger and re-
heater or refer to Point 2 in
“Troubleshooting” menu.
CO₂
External CO
2
sensor malfunction. Check that sensor is connected
properly and cable is not damaged.
In case sensor wireless – check
RS485 gateway status and sensor
status in HMI.
Contact your installation company or
place of purchase.
RH
External relative humidity sensor
malfunction.
Check that sensor is connected
properly and cable is not damaged.
In case sensor wireless – check
RS485 gateway status and sensor
status in HMI.
Contact your installation company or
place of purchase.
Output in manual mode
One or more of analogue outputs are
in manual mode.
Check Service menu for Output
settings, and check all configured
outputs to be in Auto mode. If any
outputs in Manual - change back to
Auto mode.
8.7.3 Week Schedule
The unit can be configured to operate at set airflow levels up to two time periods (00:00–23:59) on user
selected days.
Week Schedule is active only during AUTO mode.