Installation |
13
4.6.2 Condensation and Heat Insulation
Outdoor air duct and exhaust ducts must always be well insulated against condensation. Correct insulation installation
on ducts connected to the unit is especially important. All ducts installed in cold rooms/areas must be well insulated.
Use insulating covering (minimum 100 mm mineral wool) with plastic diffusion barrier. In areas with extremely low out-
door temperatures during the winter, additional insulation must be installed. Total insulation thickness must be at least
150 mm.
Caution
If the unit is installed in a cold place make sure that all joints are covered with insulation, and tape well
Duct connections/duct ends should be covered during storage and installation
Do not connect tumble dryers to the ventilation system
4.6.3 Silencers
To avoid fan noise being transferred via the duct system, silencers should be installed both on supply and extract air.
To avoid noise being transferred between rooms via the duct system and also to reduce noise from the duct system it-
self, installation of silencers before every inlet diffuser is recommended.
131677 | A004

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SystemAir Topvex SX/C Series and is the answer not in the manual?

SystemAir Topvex SX/C Series Specifications

General IconGeneral
BrandSystemAir
ModelTopvex SX/C Series
CategoryAir Handlers
LanguageEnglish

Related product manuals