TOPVERT S1 Series
E-
21
Pr5-26
{Pr5-23}
3rd Most Recent
Fault Record
2: oU
(over-voltage)
18: oH2
(Heatsink overheat)
34: rnot
(Motor selection
error)
Pr5-27
{Pr5-24}
4th Most Recent
Fault Record
3: GF
(ground fault)
19: SoFt
(Pre-charge circuit
error)
Pr5-28
5th Most Recent
Fault Record
4: SC
(IGBT failure)
20: ACI.
(ACI error)
36: LUr
(Low Voltage during
Run)
Pr5-29
6th Most Recent
Fault Record
5: oL
(drive overload)
21: ASC
(RS-485 error)
37: oUd
(over-voltage during
decel)
Pr5-30
7th Most Recent
Fault Record
6: oL1
(electronic thermal
relay 1)
22: PI.d
(PID error)
38: `x CoPY
(Parameter copy
error)
Pr5-31
8th Most Recent
Fault Record
7: ot1
(Over-Torque1)
23: Pu
(Keypad
communication
overtime)
39: LU
(Low Voltage)
Pr5-32
9th Most Recent
Fault Record
8: oCn
(over-current during
constant speed)
24: tunE
(Auto tuning failure)
40: bb
(External Base
Block )
Pr5-33
10th Most Recent
Fault Record
9: oCA
(over-current during
accel.)
25: bF
(braking chopper
failure)
Pr5-34
11th Most Recent
Fault Record
10: oCd
(over-current during
decel.)
26:(Factory
Reserved)
Pr5-35
12th Most Recent
Fault Record
11: EP1
(EPROM error 1)
27: PHL
(Phase-Loss protect
or capacitor aged)
Pr5-36
13th Most Recent
Fault Record
12: EP2
(EPROM error 2)
28: CC
(current signal error
during stop)
Pr5-37
14th Most Recent
Fault Record
13: EF
(external fault)
29: CPu
(CPU error)
Pr5-38
15th Most Recent
Fault Record
14: Ct1
(current sensor 1)
30: FAn
(Fan failure)
Pr5-39
16th Most Recent
Fault Record
15: Ct2
(current sensor 2)
31: AnI fault
(Analog input error)
Pr5-40 Full-Load Current of Motor 2
Amp (10~120% of drive’s rated current)
xxxA
100%
Pr5-41
Auto Torque Compensation of Motor
2
0.025.0%
0.0
Pr5-42 Slip Compensation of Motor 2
020 RPM
0
Pr5-43 Number of Motor Poles 2
220
4
Pr5-44 Rotor Resistance R1 of Motor 2
0.00065.535
0
0: Electronic thermal relay function
disabled
1: Inverter duty motor
(with independent cooling fan)
Pr5-45
Motor 2- Electronic Thermal Relay
Selection (oL2)
2: Standard motor
(with shaft mounted cooling fan)
0
Pr5-46
Motor 2- Electronic Thermal Relay
Characteristic
30600 Sec
60
Pr5-47
Heatsink Over-Heat pre–warning
setting (oH2)
0.0110.0
85.0
Pr5-48 Delay Time for Motor Selection
0.00~60.00 Sec
0.05