TOPVERT S1 Series
E-
19
0
Direction determined by Pr4-32
Bit 0
1
Direction determined by the master
speed
0
Without zero intervals (Continue mode)
Bit 1
1
With zero intervals (Stop mode)
0
Run zero speed when PLC Run
Paused
Bit 2
1
Run original programmed step speed
when PLC Run Paused
0
Re-Execute PLC Run from step 0 after
recover from power interruption
Pr4-33 PLC Run operation mode
Bit 3
1
Continue Execute PLC Run from the
point which power interrupted after
recover from power interruption
b01000
0~60000 : 0~60000 cycle
0= PLC Run disabled
Pr4-34 PLC Run operation cycle
60001: Continuously execute recurring cycles
0
0~15:step speed (0=master speed)
Pr4-35
What to do after PLC Run
completed
16:stop
16
0
Direction determined by Pr4-32
Bit 0
1
Direction determined by the master
speed
0
Duration of MSS Run determined by
Mix terminals.
Bit 1
1
Duration of MSS Run determined by
Pr4-15~Pr4-30 setting.
0
Without zero intervals
(Continue mode)
Bit 2
1
With zero intervals (Stop mode)
0
(Factory Reserved)
Pr4-36
Multi-Step Speed Run (MSS
RUN) operation mode
Bit 3
1
(Factory Reserved)
b00001
Group 5: Motor parameters and protection parameters
Parame
ters
Functions Settings
Factory
Setting
User
★
Pr5-00
Full-Load Current of Motor 1 Amp (10~120% of drive’s rated current)
xxxA
(100%)
Pr5-01
Auto Torque Compensation of Motor
1
0.0〜25.0% 0.0
Pr5-02
Slip Compensation of Motor 1
0〜20 RPM 0
Pr5-03
Number of Motor Poles 1
2〜20 4
Pr5-04
Rotor Resistance R1 of Motor 1
0.000〜65.535 Ω 0
0: No function
1: To execute auto-tuning and switch to
Sensorless vector control mode
★
Pr5-05 Auto-tuning & control mode selection
2: Reset to V/F control mode
0
★
Pr5-06
Low Voltage Level l
230V models:
160〜220VAC
460V models:
320〜440VAC
230V:180
460V:360
★
Pr5-07
Over-Voltage Stall Prevention Level
230V models:
320〜500VDC
460V models:
640〜1000VDC
230V:380
460V:760
Pr5-08
Software Braking Level
230V models:
320〜500VDC
460V models:
640〜1000VDC
230V:373
460V:746
0: Warn and keep operation (below 50%)
1: Warn and ramp to stop
Pr5-09 Phase-Loss Protection
2: Warn and coast to stop
0
Pr5-10
Over- Current Stall Prevention level
during accel on the constant torque
region
Amp (10~250% of drive’s rated current) A(170%)