EasyManuals Logo
Home>Toshiba>Network Hardware>TC-net 100

Toshiba TC-net 100 Installation And Wiring Manual

Toshiba TC-net 100
85 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #78 background imageLoading...
Page #78 background image
66 TC-net 100 Installation and Wiring Manual
Appendix F EMC Instructions
F
F.1 Precautions for Installation
Grounding
The grounding wire for a connector unit must be as short as possible (less than 5 cm)
and be connected to the metal part of the chassis.
I/O Cable Shielding
The digital I/O cables must be bundled and shielded with the mesh shielding jacket
(made by Kitagawa Industries, Ltd., of part No. CB-ME-40, for example) as a whole.
The analog I/O cables must also be shielded in a similar way.
These shielded cable bundles must be connected to the metal part of the cabinet with a
short grounding strap (less than 10 cm).
Shielded Cabinet
Shielded cabinets must be used for the Integrated Controllers and I/O subsystems. One
shielded cabinet model is available from VERO Electronics.
The Integrated Controllers and I/O subsystems installed in the shielded cabinet (made by
VERO Electronics, of part No. IMRAK3400, for example) have already been tested for
conformity with the EMC Specifications.

Table of Contents

Other manuals for Toshiba TC-net 100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TC-net 100 and is the answer not in the manual?

Toshiba TC-net 100 Specifications

General IconGeneral
BrandToshiba
ModelTC-net 100
CategoryNetwork Hardware
LanguageEnglish

Related product manuals