–9–
Modbus Interface
Installation Manual
7 Test run check
Before starting test run
• Set the indoor unit central control address so that it does not match any other indoor unit addresses.
• Be sure to press the reset switch SW7 on the Modbus Interface when the indoor unit central control address
setting has been changed or added.
Test run
(1) Check the communication status between Modbus Interface and indoor unit or TCB-IFCG1TLE with LED5.
Check that the communication between Modbus Interface and each indoor unit or TCB-IFCG1TLE connected
is normally performed by selecting an indoor unit or TCB-IFCG1TLE using SW1 to SW3.
Confirming procedure:
• Set bit2 of SW3 to “ON” during normal operation.
• Set the central control address of the target indoor unit with SW1 and SW2. Set SW1 and SW2 according to
the “Indoor unit central control address and SW1/SW2 setting” table below.
• Communication status is displayed by LED5.
Indoor unit or TCB-IFCG1TLE central control address and SW1/SW2 setting
Communication status with indoor unit LED5 Remarks
Normal Lighting
Error Blinking
Communication with the indoor unit was established
previously, but is disabled currently.
Invalid indoor unit Light off
Communication with the indoor unit has never been
established.
(Example) Check the communication status of indoor unit with a central control address of 41.
Set bit1 of SW3 to “ON”, SW2 to “2” and SW1 to “8”.
Indoor unit
central control
address
SW2 SW1
Indoor unit
central control
address
SW2 SW1
Indoor unit
central control
address
SW2 SW1
Indoor unit
central control
address
SW2 SW1
1 00171033204930
2 01181134215031
3 02191235225132
4 03201336235233
5 04211437245334
6 05221538255435
7 06231639265536
8 07241740275637
9 08251841285738
10 09 26 19 42 29 58 39
11 0 A 27 1 A 43 2 A 59 3 A
12 0 B 28 1 B 44 2 B 60 3 B
13 0 C 29 1 C 45 2 C 61 3 C
14 0 D 30 1 D 46 2 D 62 3 D
15 0 E 31 1 E 47 2 E 63 3 E
16 0F 32 1F 48 2F 64 3F
9-EN