4. Parameters
4.1.
Communication parameters
This option doesn't operate if these parameters are not correctly set.
4.1.1. Relation parameters for VF-S15/MB1
Title
Communi
cation No.
Function Description
Default
setting
cmod
0003 Command mode selection
0: Terminal board
1: Panel keypad (including remote keypad)
2: RS485 communication
3: CANopen communication
4: Communication option
1
fmod
0004
Frequency setting mode
selection 1
0: Setting dial 1 (save even if power is off)
1: Terminal board VIA
2: Terminal board VIB
3: Setting dial 2 (press in center to save)
4: RS485 communication
5: UP/DOWN from external logic input
6: CANopen communication
7: Communication option
8: Terminal board VIC
9, 10: -
11: Pulse train input
12, 13: -
14:
sr0
0
f519
0519
Setting of acceleration /
deceleration time unit
0: -
1: 0.01s unit (after execution: 0)
2: 0.1s unit (after execution: 0)
0
(*1)
f749
0749
Integrating wattmeter display
unit selection
0: 1.0=1kWh
1: 1.0=10kWh
2: 1.0=100kWh
3: 1.0=1000kWh
4: 1.0=10000kWh
(*2)
f856
0856
Number of motor pole pair for
communication
1: 2 poles
2: 4 poles
3: 6 poles
4: 8 poles
5: 10 poles
6: 12 poles
7: 14 poles
8: 16 poles
2
f898
0898 Reset mode selection (*3)
0: Clear trip without disrupting communication by
reset command from communication option.
Reset and restart by reset command from panel
keypad, terminal block or RS485 communication.
1: Reset
2: Clear trip
3 to 5: -
0
f899
0899 Communication function reset
0: -
1: Reset (after execution: 0)
-
(*1): 0.1s unit is selected as default setting.
(*2): Default setting values vary depending on the capacity.
(*3): When you reset by
f899
=1 setting, or trip is requires a reboot of inverter, the inverter is rebooted
regardless of the parameter setting.