K-39
E6581386
11
[Output terminal function setting (1/3)] Sensorless vector/PG feedback control (●: valid, -: invalid)
Positive
logic
Negative
logic
Function Vector control PM control V/f Reference
0 1 LL
●/●
● ●
2 3 UL
●/●
● ●
4 5 LOW
●/●
● ●
6 7 Acceleration/deceleration completion
●/●
● ●
8 9 Specified speed arrival
●/●
● ●
10 11 Failure FL (all trip)
●/●
● ●
12 13 Failure FL (except for EF, OCL, EPHO and OL2)
●/●
● ●
14 15 Overcurrent pre-alarm
●/●
● ●
16 17 Inverter overload pre-alarm
●/●
● ●
18 19 Motor overload pre-alarm
●/●
● ●
20 21 Overheat pre-alarm
●/●
● ●
22 23 Overvoltage pre-alarm
●/●
● ●
24 25 Main circuit undervoltage alarm
●/●
● ●
26 27 Low current alarm
●/●
● ●
28 29 Overtorque alarm
●/●
● ●
30 31 Braking resistor overload pre-alarm
●/●
● ●
32 33 In emergency stop
●/●
● ●
34 35 In course of retry
●/●
● ●
38 39 PID deviation limit
●/●
● ●
40 41 Run/Stop
●/●
● ●
42 43 Serious failure (OCA, OCL, EF, phase failure, etc.)
●/●
● ●
44 45 Light failure (OL, OC1, 2, 3, OP)
●/●
● ●
46 47
Commercial/INV switching output 1 (for inverter
operation output)
●/●
● ●
48 49
Commercial/INV switching output 2 (for commercial
operation output)
●/●
● ●
50 51 Cooling fan ON/OFF
●/●
● ●
52 53 In Jog run
●/●
● ●
54 55 Panel operation/terminal board operation switching
●/●
● ●
56 57 Cumulative operation time alarm
●/●
● ●
58 59 PROFIBUS/DeviceNet/CC-Link communication error
●/●
● ●
60 61 Forward/reverse run
●/●
● ●
62 63 Ready for operation 1
●/●
● ●
64 65 Ready for operation 2
●/●
● ●
70 71 In (pre-)alarm status
●/●
● ●
76 77 Inverter healthy output
●/●
● ●
78 79 RS485 communication error
●/●
● ●