76 UV-PRC001-EN
Performance Data
DK, R1, R2-Coil Cooling
Table P11: 4-pipe DK coil, CW cooling data
Unit Size Coil
Type
Cooling (80 EDB/67 EWB, 45 EWT/55 LWT)
TMBH SMBH GPM WPD
075
DK
16.60 13.30 3.33 1.30
100 24.70 18.30 4.94 3.10
125 34.00 24.50 6.79 6.30
150 39.40 27.70 7.87 9.20
200 45.24 33.11 9.04 11.83
Table P12: 4-pipe R1, R2 coil, CW cooling data
Unit Size Coil
Type
Cooling (80 EDB/67 EWB, 45 EWT/55 LWT)
TMBH SMBH GPM WPD
075
R1 25.19 17.89 5.04 3.82
R2 28.08 19.79 5.62 4.62
100
R1 35.52 24.60 7.10 8.40
R2 39.29 27.12 7.86 10.04
125
R1 41.75 29.61 8.35 4.85
R2 46.73 32.88 9.35 5.93
150
R1 52.11 36.32 10.42 8.11
R2 58.02 40.24 11.60 9.82
200
R1 62.79 44.78 12.56 11.32
R2 71.72 50.61 14.34 14.37