RLC-SVX14H-GB
30
RTUD Installation
The installation of a split system offers a good economic
alternative to satisfy the chilled water demand for
cooling a building, particularly in the case of new
construction.
Releasing the Nitrogen Holding Charge
The nitrogen holding charge can be released into the
atmosphere.
CAUTION! When releasing nitrogen holding charge,
ventilate the room. Avoid breathing in the nitrogen.
Application examples
No Elevation Difference
Figure 8 - No Elevation Difference
RESTRICTIONS
Total distance between components should not
exceed 61 m (actual) or 91 m (equivalent).
Liquid line height must not exceed 4.5 m from the
base of the air-cooled condenser unit.
Discharge line trap is recommended leaving the oil
separator if the discharge piping runs for more than
3 m (actual)horizontally above the RTUD unit.
Split system installation