RLC-SVX14H-GB
31
Split system installation
Condenser Above the Compressor Chiller
Figure 9 - Condenser above the compressor chiller
RESTRICTIONS
Total distance between components should not
exceed
61 m (actual) or 91 m (equivalent).
Elevation difference greater than 30 m (actual) will
result in at least a 2% effi ciency decrease.
Inverted Trap
Height equal to
top of Condenser
Trap
Liquid Line
Discharge Line
Liquid Line
Discharge Line
Inverted Trap
Heght equal to
top of Condenser