RLC-SVX14H-GB
9
General data
Table 1 - RTWD Standard Effi ciency - R134a
RTWD RTWD RTWD RTWD
160 170 190 200
Indicative performances
Cooling Capacity (1) (kW) 582.0 642.0 700.0 769.0
Total Power input in cooling (1) (kW) 133.0 149.0 161.0 174.0
Heating Capacity (2) (kW) 568.3 624.2 679.8 746.8
Total Power input in heating (2) (kW) 138.3 154.1 167.0 181.7
Compressor
Compressor Number per Circuit # 1/1 1/1 1/1 1/1
Type Screw
Model M2/N1 N1/N1 N1/N2 N2/N2
Evaporator
Quantity # 1
Type Flooded shell and tube heat exchanger
Evaporator model E3BM2 E3BM1 E3BM1 E3BMJ
Evaporator Water Content volume (l) 69.4 75.5 84.0 90.1
Two pass evaporator
Evap. Water Flow rate - Minimum (3) (l/s) 8.4 9.3 10.6 11.5
Evap. Water Flow rate - Maximum (3) (l/s) 30.7 34.1 38.9 42.3
Nominal water connection size (Grooved coupling) (in) - (mm)
5 1”
(139.7 mm)
5 1”
(139.7 mm)
5 1”
(139.7 mm)
5 1”
(139.7 mm)
Three pass evaporator
Evap. Water Flow rate - Minimum (3) (l/s) 5.6 6.2 7.1 7.7
Evap. Water Flow rate - Maximum (3) (l/s) 20.4 22.7 25.9 28.2
Nominal water connection size (Grooved coupling) (in) - (mm)
4”
(114.3 mm)
4”
(114.3 mm)
4”
(114.3 mm)
4”
(114.3 mm)
Condenser
Quantity # 1
Type Shell and Tube Heat Exchanger
Condenser model C3BM2 C3BM2 C3BM1 C3BMJ
Condenser Water Content volume (l) 87.5 93.6 102.9 111.1
Two pass condenser
Cond. Water Flow rate - Minimum (l/s) 11.0 12.1 13.6 15.0
Cond. Water Flow rate - Maximum (l/s) 40.4 44.2 49.9 55.0
Nominal water connection size (Grooved coupling) (in) - (mm)
6”
(168.3 mm)
6”
(168.3 mm)
6”
(168.3 mm)
6”
(168.3 mm)
Dimensions (4)
Unit Length (mm) 3490 3490 3490 3490
Unit Width (mm) 1310 1310 1310 1310
Unit Height (mm) 1970 1970 1970 1970
Weights (5)
Shipping Weight (kg) 3718 3881 3900 3924
Operating Weight (kg) 3874 4049 4086 4125
System data (6)
Nb of refrigerant circuit # 2 2 2 2
Minimum cooling load % % 30 30 30 30
Standard unit
R134a refrigerant charge Circuit1 / Circuit 2 (6) (kg) 65/67 65/65 65/67 65/66
Oil charge Circuit1 / Circuit 2 (l) 9.9/11.7 11.7/11.7 11.7/11.7 11.7/11.7
POE Oil type OIL048E or OIL023E
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser water temperature 30°C/35°C - for detailed performances consult
order write up.
(2) Indicative performance at Evaporator water temperature: 10°C / 7°C - Condenser water temperature 40°C/45°C - for detailed performances consult
order write up.
(3) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(4) These dimensions are the maximum for a specifi c size, they may vary from one confi guration to another within a same size. For accurate
dimensions of a specifi c confi guration, refer to relevant submittal drawings.
(5) All weights +/-5% and are the maximum for each size and may vary from one confi guration to another for the same size (add 62kg for unit with
acoustic package) and refer to relevant drawing for a specifi c confi guration.
(6) System data are indicative and subject to change without notice. Please refer to unit nameplate data.