BAS-SVX46E-EN
27
Voltage Inputs
Checkout Procedure Measurement
Expected Value
Step 1
Measure AC voltage across the
voltage termination
VAC 0.0 V
AC voltage will affect further
measurement
Step 2
Measure DC voltage across the
voltage termination
Compare to input status in Tracer
TU
Current Inputs
Method 1
General Information
Checkout
Procedure Measurement
Expected Value
Method 1 capitalizes on the very
low input resistance of a DMM in
current measurement mode.
However, this method affects the
value that the expansion module
will use while controlling outputs.
When the meter is set to current
mode, the current flowing into the
expansion module circuit will drop
to zero or near zero.
Step 1
Measure AC voltage across the
current input
VAC 0.0 V
AC voltage will affect further
measurement
Step 2
Measure DC current across the
current input
Compare to input status in Tracer TU
CCoommmmiissssiioonniinngg aanndd TTrroouubblleesshhoooottiinngg iinn aa PPoowweerreedd SSttaattee

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane Tracer XM30 and is the answer not in the manual?

Trane Tracer XM30 Specifications

General IconGeneral
BrandTrane
ModelTracer XM30
CategoryControl Unit
LanguageEnglish

Related product manuals