26 BAS-SVX40A-EN
Troubleshooting
8. Attach the terminal block on the wiring harness to the receptacle on the new WCI and route the
wires as before (through either the back plate or the bottom exit port).
9. If a Tracer SC is present on the network, restore power to the Tracer SC. The network will re-
form itself.
New coordinator WCI when no Tracer SC is present
10. Set (or verify if pre-addressed) the rotary address switches on the new WCI.
11. Attach the terminal block on the wiring harness to the receptacle on the new WCI and route the
wires as before (through either the back plate or the bottom exit port).
12. Using a USB cable, connect Tracer TU to another WCI on the network and disband the network
(see
“Disbanding a Network,” p. 23).
13. Restore power to the controller that the WCI is installed on.
14. Push the START button for 5 seconds or use Tracer TU to re-form the network.