Model No. : UT-101 F
PAGE:5
This Mode is used to change Input , Relay and Communication Operation
Configuration
Parameter
Description
Range
Default Value
CONFIGURATION MODE PARAMETER
CONF
Password for Parameter Setting
Values between
Mode
0000
0000
Password for Configuration Parameter
0000 to 9999
Input Type
1NP
pt-1
Down the type by key or Up by key.
Pt-1
pt-1 : PT-100 (RTD)
1-5v :Linear1-5VDC
0-20 : Linear0-20mADC
4-20 : Linear4-20mADC
TTC.
STC.
R TC.
. TC
JTC.
: T Type Thermo-Couple
: ‘S’ Type Thermo-Couple
: ‘R’ Type Thermo-Couple
: ‘K’ Type Thermo-Couple
: J’ Type Thermo-Couple
. : Linear 0.5-2.5 V DC25v
: Linear0-10VDC10v
CU53 : CU-53 COPPER SENSOR
ETC.
: ‘E’ Type Thermo-Couple
(As per Reqd.)
4
Scroll the digit by key, increase by key.
Selection of input of the Instrument.
1. CONFIGURATION MODE
Decimal Point Selection
: No decimal(1234)
DP
0001
0001
Increase digit by key, decrease by key
0000
Alarm 1 Relay Action.
: Active in High
TSP1
L oN
LoN
Changethetypeby or key.
HoN
ON
OFF
PV
SV
ON
OFF
PV
SV
LON:
: Active in Low
LoN
HON:
Alarm 2 Relay Action.
TSP2
L oN
LoN
Changethetypeby or key.
: One decimal(123.4)
0001
: Two decimal(12.34)
0002
: Three decimal(1.234)
0003
: Active in High
HoN
: Active in Low
LoN
Active same as above
Dead Band
: Selected
dEAd
no
no
YES
: Not Selected
no
Changethetypeby or key.
Only one relay get operated in this parameter, relay
get active on set point 1 value and deactive in set
point-2value. Used for Level & Fan control.
SV-Hyst
SV+Hyst
CTC.
: C’ Type Thermo-Couple
Baud Rate
baud
9600
9600
4800 : Baud rate 4800
Change the Rate by or key.
9600 : Baud rate 9600
192K : Baud rate 19200
Node Address
Values between
nAdd
0001
00010000 to 0127
Increase digit by key, decrease by key
Device address for Communication