No. 465
FST error: Total timeout, depressurising
Description
The valve is at the fail position but the pressure does not reach 0 bar.
Trouble shooting
This error can be caused by:
Blocked exhaust
Offset in the calibration of the analogue input
Sensor error
It can be solved by:
Resolve the mechanical problem
Verify that the measured pressure value is zero when unpressurised
Increase Depressurising timeout