EasyManuals Logo
Home>Val Controls>Controller>IDC24-AF

Val Controls IDC24-AF User Manual

Default Icon
74 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #53 background imageLoading...
Page #53 background image
DID-UM-002
Val Controls A/S Limfjordsvej 3 DK-6715 Esbjerg N Tel. +45 7547 0600
vc@valcontrols.com www.valcontrols.com
Revision: 10
53/74
No. 466
FST error: Total timeout, position
Description
The valve did not reach the operational position within the FST total timeout
Trouble shooting
This error can be caused by:
No supply pressure
The valve is stuck
The valve is moving slow
The solenoid valve cannot be activated
It can be solved by:
Resolve the mechanical problem
Increase FST total timeout

Other manuals for Val Controls IDC24-AF

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Val Controls IDC24-AF and is the answer not in the manual?

Val Controls IDC24-AF Specifications

General IconGeneral
BrandVal Controls
ModelIDC24-AF
CategoryController
LanguageEnglish

Related product manuals