5.4.3 Pump Control menu
Pump Control Default Values Reset Description
1 Pump
1 Output None A Configure pump output signal
2 Controller The status of the pump controller
1 Always off A The pump is always off
2 Always on The pump is always on
3 Auto The pump controller is active
4 Manual Manual control the pump
3 Motor safety relay None A Select the input signal
4 Max running time Configure the max running time
1 Status Off On/off Status of the maximum running time function
2
Time
120 0-255 sec A Set the time the pump is active before a warning appears
2
Pressure
1
Loop
Configuration if using a pressure transmitter
1 Pump configuration Configure the levels which starts and stops the pump
1 Pump start 80 bar 0 - 500 bar A Start pump when pressure is below this value
2 Pump stop 120 bar 0 - 500 bar A Stop the pump when the pressure is above this value
3 Level
1
Loop
Configuration if using a level transmitter
1 Pump stop 100 mm 0-9999 mm A Stop the pump when the level is below this value
2 Loop configuration Configure the connected level transmitter
1 Loop 4mA value 0 mm 0-9999 mm A Level at 4mA
2 Loop 20mA value 700 mm 0-9999 mm A Level at 20mA
4 Temperature
1
Loop
Configuration if using a temperature transmitter
1 Pump stop high Pump stop high cofiguration
1 Status Off On/off Turn the pump stop high function on and off
2 Pump stop
80 °C
-200 - 850 °C A Stop the pump when the temperature is above this value
2 Pump stop low Pump stop low cofiguration
1 Status Off On/off Turn the pump stop low function on and off
2 Pump stop
-20 °C
-200 - 850 °C A Stop the pump when the temperature is below this value
5 Valve
1 Pump start
1 Valve open Start pump when valve opens
2 Valve close Start pump when valve closes
3 Valve stayput Start pump when valve goes to stayput
2 Pump stop
1 Delay 5 sec 0-240 sec Keeps the pump running after start command has ended
More settings are available through ValConnect.

Other manuals for Val Controls IHP24-B

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Val Controls IHP24-B and is the answer not in the manual?

Val Controls IHP24-B Specifications

General IconGeneral
BrandVal Controls
ModelIHP24-B
CategoryValve Positioners
LanguageEnglish

Related product manuals