Sensor signal is too noisy
The sensor signal is too noisy, even if the deadband has been set to 10%
• Improve signal quality
• Increase the travel
A timeout occurred during the calibration
The system behaves in an unexpected way.
• Slow down the system
Restart the calibration
The positioner is not able to hold the actuator at a 50%
• Check solenoid settings
• Check for leakages in the hydraulic system
• If the system is fast (travel time <3). Slow system down
• Restore ESD signal
• Disable ESD functionality in the advanced menu