DHP-UM-020
Val Controls A/S Limfjordsvej 3 DK-6715 Esbjerg N Tel. +45 7547 0600 Fax +45 7547 0611
vc@valcontrols.com www.valcontrols.com
Revision: 12
33/38
No. 206
Sensor signal is too noisy
Description
The sensor signal is too noisy, even if the deadband has been set to 10%
Trouble shooting
Improve signal quality
Increase the travel
No. 207
Calibration timeout
Description
A timeout occurred during the calibration
Trouble shooting
The system behaves in an unexpected way.
Slow down the system
Restart the calibration
No. 208
Hold test failed
Description
The positioner is not able to hold the actuator at a 50%
Trouble shooting
Check solenoid settings
Check for leakages in the hydraulic system
If the system is fast (travel time <3). Slow system down
7.3 External connections
No. 301
ESD signal
Description
The ESD signal is low
Trouble shooting
Restore ESD signal
Disable ESD functionality in the advanced menu

Other manuals for Val Controls IHP24-B

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Val Controls IHP24-B and is the answer not in the manual?

Val Controls IHP24-B Specifications

General IconGeneral
BrandVal Controls
ModelIHP24-B
CategoryValve Positioners
LanguageEnglish

Related product manuals