No. 468
FST error: At 0% position
Description
The 0% switch was activated before the 100% switch was released
Trouble shooting
This error can be caused by:
Position sensor was disconnected
Position sensor is operating in the illegal area
Wrong configuration of the position switches
The valve moved from 100% directly to 0%
It can be solved by:
Check the position sensor
Make sure the position sensor is operating within the legal area
Check the function of the position switches