EasyManuals Logo
Home>Val Controls>Controller>IHP24-F

Val Controls IHP24-F User Manual

Val Controls IHP24-F
74 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #67 background imageLoading...
Page #67 background image
DID-UM-002
Val Controls A/S Limfjordsvej 3 DK-6715 Esbjerg N Tel. +45 7547 0600
vc@valcontrols.com www.valcontrols.com
Revision: 10
67/74
9.1 Pump unit errors
No. 601
Pump control: Low level.
Description
The measured level is below the specified value.
Trouble shooting
This error can be caused by:
Low oil level
Mal functioning sensor
High value of Level Low limit
It can be solved by:
Refill the tank with oil
Decrease Level Low limit value
No. 602
Pump control: Temperature.
Description
The measured temperature is above or below the limit values.
Trouble shooting
This error can be caused by:
Low oil temperature
High oil temperature
Sensor malfunction
It can be solved by:
Change oil temperature
Adjust temperature Low limit
Adjust temperature High limit
No. 610
Pump control: Motor safety relay
Description
The motor protection relay is active
Trouble shooting
This error can be caused by:
Motor safety relay has been activated
Motor safety relay malfunction or disconnected

Other manuals for Val Controls IHP24-F