EasyManuals Logo
Home>Val Controls>Controller>IHP24-F

Val Controls IHP24-F User Manual

Val Controls IHP24-F
74 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #62 background imageLoading...
Page #62 background image
DID-UM-002
Val Controls A/S Limfjordsvej 3 DK-6715 Esbjerg N Tel. +45 7547 0600
vc@valcontrols.com www.valcontrols.com
Revision: 10
62/74
8.5 Solenoid valve test errors (501 to 514)
No. 501
SOT start condition: Not at operational
Description
The valve is not at the operational position
Trouble shooting
This error can be solved by
Make sure the valve is at the operational position
Perform an endpoint calibration.
Increase the solenoid test position deadband
No. 502
SOT start condition: Low start pressure
Description
The measured pressure is below Start pressure low
Trouble shooting
This error can be solved by:
Increase the pressure in the system
Decrease the Start pressure low
No. 503
SOT start condition: High start pressure
Description
The measured pressure is above Start pressure high
Trouble shooting
This error can be solved by:
Decrease the pressure in the system
Increase Start pressure high
No. 504
SOT start condition: In ESD mode
Description
Emergency shutdown is detected
Trouble shooting
This error can be solved by:
Activate the ESD input
No. 506
Aborted by the user
Description
The test was aborted by the user
Trouble shooting
This error can be solved by:
Perform a new SOT

Other manuals for Val Controls IHP24-F

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Val Controls IHP24-F and is the answer not in the manual?

Val Controls IHP24-F Specifications

General IconGeneral
BrandVal Controls
ModelIHP24-F
CategoryController
LanguageEnglish

Related product manuals