8.2.4 Removing Fan Assembly
Do not attempt to remove the fan assemblies without first contacting Vertiv Technical Support at 1-800-
222-5877.
8.3 Condensate-drain and Condensate-pump System Maintenance
8.3.1 Condensate Drain
Check for and clear obstructions in tubing during routine maintenance.
8.3.2 Condensate Pump
WARNING! Risk of electric shock. Can cause injury or death. Open all local and remote electric
power-supply disconnect switches and verify that power is Off with a voltmeter before working
within the condensate pump electrical connection enclosure. The Lieber iCOM does not
isolate power from the unit, even in the Unit Off mode. Some internal components require and
receive power even during the “Unit Off” mode of the LieberiCOM.
To maintain the condensate pump:
1. Disconnect power to the unit using the disconnect switch.
2. Check for and clear obstructions in gravity lines leading to the condensate pump.
3. Remove the sump, clean with a stiff nylon brush and flush with water.
4. Inspect and clear clogs in the discharge check valve and float mechanism.
5. Reassemble and check for leaks.
Vertiv | Lieber CW™ Installer/User Guide
38