EasyManuals Logo
Home>Vertiv>Power Supply>NetSure 731 A91

Vertiv NetSure 731 A91 User Manual

Vertiv NetSure 731 A91
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #20 background imageLoading...
Page #20 background image
12 Chapter 3 Commissioning
NetSure 731 A91 Subrack Power System User Manual
3.2 Basic Settings
When the system is put into service for the first time, the parameters of controller module must be set based on the
actual system configuration, such as battery number, capacity, user’s charge current limit and other functional
requirements. Only after that can the controller module display system operation information and control the output.
M830B controller password is 640275. System parameter settings are shown in Table 3-1.
Table 3-1 M830B controller paremeter settings
Parameter
Path
Default settings
Capacity
NCU home pageSettingsBattery chargeBattery 1 capacity
300Ah
LVD1 enabled
LCDSettingsLVD SettingsLVD1 enabled
Enabled
LVD2 enabled
LCDSettingsLVD SettingsLVD2 enabled
Enabled
LVD1
LCDSettingsLVD SettingsLVD1 Volt
44.0V
LVD2
LCDSettingsLVD SettingsLVD2 Volt
43.2V
AC Fail Required
WebAdvanced SettingsSystemLVD GroupAC Fail Required
Y
Num Batt Shunts
LCDSettingsBat. SettingsBasic SettingsNum Batt Shunts
1
Batt shunts settings
LCDSettingsBat. SettingsBasic SettingsBattery 1Shunt
Current/Shunt Voltage
600A/25mV
Contactor type
WebSettingsLVDContactor type
Monstabillity
Walk-in
LCDSettingsRect SettingsWalk-in on
Y
Walk-in T
LCDSettingsRect SettingsWalk-in T
128S
Note: The above battery protection voltage should be set according to the battery manufacturer's requirements. The battery
capacity should be set according to the actual configuration.
M530B controller password is 640275. System parameter settings are shown in Table 3-2.
Table 3-2 M530B controller main paremeter settings
Parameter
Path
Default settings
System Type
Quick Settings System Type
48V/SET
Capacity
Quick Settings Capacity
150Ah
LVD2
SettingsBat. SettingsLVD Settings LVD2 Volt
43.2V
LVD1
SettingsBat. SettingsLVD Settings LVD1 Volt
44.0V
Batt shunts settings
Settings Basic Settings Batt Shunts 1
N
Batt shunts settings
Settings Basic Settings Batt Shunts 2
Y
BLVD contactor
Bat. Settings LVD Settings BLVD Volt
43.2V
AC Phase
SettingsInput SettingsAC PH
3-PH
Walk-in
SettingsRect SettingsWalk-in on
N
Walk-in T
SettingsRect SettingsWalk-in T
8S
Note: The above parameters need to be adjusted according to the actual situation.
3.3 Alarm Check And System Operation Status Check
Alarm check
Check that all functional unit can trigger alarms that can be displayed on the controller.
OK
Comment
Pull out one rectifier. The ‘Rect N Com Failure’ alarm should be triggered. Insert the rectifier in. The alarm
should disappear. Repeat the same procedures on other rectifiers
Switch off battery MCB 1. The ‘Batt1 Failure’ alarm should be triggered. Switch on the MCB. The alarm
should be cleared. Repeat the same on battery MCB 2, MCB 3 and MCB 4.
Switch off a load MCB connected to a load route. The alarm ‘Load Fuse N Failure’ should be triggered.
Switch on the MCB, and the alarm should be cleared. Repeat the same on the other load MCBs
Remove all the battery MCBs. Keep only one rectifier in operation. Through the controller module, adjust
the rectifier FC voltage to make it lower than the alarm point. The alarm ‘DC Voltage Low’ should be
triggered

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vertiv NetSure 731 A91 and is the answer not in the manual?

Vertiv NetSure 731 A91 Specifications

General IconGeneral
BrandVertiv
ModelNetSure 731 A91
CategoryPower Supply
LanguageEnglish

Related product manuals