This section is intended to provide operating
instructions and information for users.
Section Contents
Operating the Boiler . . . . . . . . . . . . . . . . . . . . . .5
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . 12
Operating the Boiler
Prevent Combustion Air Contamination
!
If the boiler combustion air inlet is located in any
area likely to cause contamination, or if products
which would contaminate the air cannot be
removed, you must have the combustion air and
vent repiped and terminated to another location.
Contaminated combustion air will damage the
boiler, and can result in severe personal injury,
death, or substantial property damage.
To prevent potential of severe personal injury or
death, check for products or areas listed in Table 1
before installing boiler. If any of these contaminants
are found:
• remove contaminants permanently.
— OR —
• isolate boiler and provide outside combustion air.
See national, provincial or local codes for further
information.
Operating Instructions
See the warnings and operating instructions on the
following pages to start and turn o the boiler. See
Table 2 to locate the correct Operating Instructions for
the gas valve model installed on your boiler.
(continued on the next page)
Operation
Draft - For Engineering Review ONLY Jan. 2023 HC
Products to avoid
Spray cans containing chloro/
uorocarbons
Paint or varnish removers
Permanent wave solutions
Hydrochloric acid and muriatic
acid
Chlorinated waxes and cleaners Cements and glues
Chlorine-based swimming pool
chemicals
Anti-static fabric softeners used in
clothes dryers
Calcium chloride used for thawing
Chlorine-type bleaches,
detergents, and cleaning solvents
Sodium chloride used for water
softening
Adhesives used to fasten building
products and other similar products
Refrigerant leaks Excessive dust and dirt
Areas likely to have contaminants
Laundry and dry cleaning areas
and establishments
Auto body shops
Swimming pools Plastic manufacturing plants
Metal fabrication plants
Furniture renishing areas and
establishments
Beauty shops New building construction
Refrigeration repair shops Remodeling areas
Photo processing plants Garages with workshops
Table 1 Corrosive contaminants and sources
Table 2 Operating instructions guide
Spark-ignited pilot Models Page
Honeywell VR8204/VR8304
CGa-25 thru CGa-8
EG-30 thru EG-75
PEG-30 thru PEG-55
6
CGi-3 thru CGi-6
10
White-Rodgers 36E
CGa-25 thru CGa-6
EG-30 thru EG-50
PEG-30 thru PEG-50
7
CGi-3 thru CGi-6
10
White-Rodgers 36C
CGa-7 & CGa-8
EG-55 thru EG-75
PEG-55
8
CGi-3 thru CGi-6
10
Robertshaw 7200
CGa-25 thru CGa-6
EG-30 thru EG-50
PEG-30 thru PEG-50
9
–– LGB