1. Explosion Protection Instrumentation
1-6
TI 32S01J30-01E
Connection of FIO equipment for US (FM) and Canada (FM)
ProSafe-RS/ProSafe-RS Lite NI-compliant equipment can be connected to the NI-compliant
devices installed in Division 2. For the connection to an NI-compliant device, it is necessary
to compare parameters between the device installed in a hazardous area and ProSafe-RS/
ProSafe-RS Lite I/O module and evaluate whether connection is possible or not.
ProSafe-RS/ProSafe-RS Lite equipment can be connected to the ameproof devices installed
in Division 1 / Division 2 with explosion-proof wiring that is dened in NEC (National Electrical
Code), CEC (Canadian Electrical Code) or the rules/standards of each country or region. (*1)
*1: SCB100 / SCB110 shall not be installed in Division 1.
When using SCB100/SCB110 to perform eld wiring diagnosis to the eld device installed in Division 1, it is necessary to prepare
an element that has the same characteristics as SCB100/SCB110 and is compatible with Division 1 installation. When using
these elements to realize the wiring diagnosis of the DI function, check the behavior with the actual connection environment
before using. Please contact with Yokogawa about the specication of SCB100/SCB110.
Division 1 Division 2 Non-Hazardous Area
Flameproof
device
SNU
NI-compliant
device
F010303E.ai
*1
*1: Explosion-proof wiring that is dened in NEC, CEC or the rules/standards of each country or region.
Figure NI (Installation in Non-Hazardous Area)
ProSafe-RS/ProSafe-RS Lite NI-compliant equipment can be installed in Division 2 by mounting
in a keyed metal cabinet approved by approval authorities.
Division 1 Division 2
Flameproof
device
SNU
NI-compliant
device
F010304E.ai
*1
*1: Explosion-proof wiring that is dened in NEC, CEC or the rules/standards of each country or region
Figure NI (Installation in Division 2)
Dec 3, 2021-00

Table of Contents

Other manuals for YOKOGAWA ProSafe-RS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YOKOGAWA ProSafe-RS and is the answer not in the manual?

YOKOGAWA ProSafe-RS Specifications

General IconGeneral
BrandYOKOGAWA
ModelProSafe-RS
CategoryIndustrial Equipment
LanguageEnglish

Related product manuals