1. Explosion Protection Instrumentation
1-7
TI 32S01J30-01E
Dec 3, 2021-00
Overview of Connecting N-IO Components
Overview of Connecting S2BN1D base plate for ATEX, IECEx, and UKEX
S2BN1D Base plate can be connected to the intrinsic safety device installed in Zone 0, Zone 1,
and Zone 2 using a barrier and explosion-proof wiring as shown in the following gures.
They can be connected to Intrinsic safety device installed in Zone 0, 1, and 2 using Explosion-
proof wiring that is dened in IEC/EN 60079-14 and the rules/standards of each country or
region.
S2BN1D base plate can be connected to the Ex “ec”/Type “n” devices installed in Zone 2 with
explosion-proof wiring that is dened in IEC/EN 60079-14 and the rules/standards of each
country or region.
S2BN1D base plate can be connected to the ameproof devices installed in Zone 1 / Zone 2
with explosion-proof wiring that is dened in IEC/EN 60079-14 and the rules/standards of each
country or region. (*1)
N-IO node unit including S2BN1D and SCU or node unit (24 V DC feeding type) can be installed
in Zone 2 by mounting in a keyed metal cabinet with protection rating of IP54 or higher.
N-IO eld enclosure S2NN70D is equipped with S2BN1D inside the enclosure, thus the following
gure is also applicable to S2NN70D. In the case of S2NN70D, replace S2BN1D with S2NN70D.
*1: SCB100 / SCB110 shall not be installed in Zone 1.
When using SCB100/SCB110 to perform eld wiring diagnosis to the eld device installed in Zone 1, it is necessary to prepare
an element that has the same characteristics as SCB100/SCB110 and is compatible with Zone 1 installation. When using these
elements to realize the wiring diagnosis of the DI function, check the behavior with the actual connection environment before
using. Please contact with Yokogawa about the specication of SCB100/SCB110.
S2BN1D Base plate
F010305E.ai
Zone1 Zone2 Non-Hazardous AreaZone0
Safety
Barrier
Safety
Barrier
Safety
Barrier
Flameproof
device
Intrinsic safety
device
Ex "ec"
Type “n”
device
Intrinsic safety
device
Intrinsic safety
device
*1
*1
*1
*1
*1
*1: Explosion-proof wiring that is dened in IEC/EN 60079-14 or the rules/standards of each country or region.
Figure Connection of S2BN1D for ATEX, IECEx, and UKEX (1)

Table of Contents

Other manuals for YOKOGAWA ProSafe-RS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YOKOGAWA ProSafe-RS and is the answer not in the manual?

YOKOGAWA ProSafe-RS Specifications

General IconGeneral
BrandYOKOGAWA
ModelProSafe-RS
CategoryIndustrial Equipment
LanguageEnglish

Related product manuals