EasyManuals Logo
Home>York>Air Conditioner>20 Series

York 20 Series User Manual

York 20 Series
68 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #43 background imageLoading...
Page #43 background image
349215-JIM-B-1008
Johnson Controls Unitary Products 43
FIGURE 19 - CHARGING CHART - 20 TON
20 Ton Char
g
in
g
Chart
100
150
200
250
300
350
400
60 65 70 75 80 85 90 95 100
Suction Pressure (psi)
Discharge Pressure (psi)
115°
105°
95°
85°
75°
65°
Outdoor Temp (°F)
1. Make sure that both condenser fans are running when charging. One fan may switch
off at lower ambient temperatures making the chart above inaccurate.
2. This chart is applicable to unit with the TXV's left to the factory setting. If the TXV's
have been adjusted in the field, the charging chart may no longer apply.
FIGURE 20 - CHARGING CHART - 25 TON
25 Ton Char
g
in
g
Chart
100
150
200
250
300
350
400
60 65 70 75 80 85 90 95 100
Suction Pressure (psi)
Discharge Pressure (psi)
115°
1
05°
95°
85°
75°
65°
Outdoor Temp (°F)
1. Make sure that both condenser fans are running when charging. One fan may switch
off at lower ambient temperatures making the chart above inaccurate.
2. This chart is applicable to unit with the TXV's left to the factory setting. If the TXV's
have been adjusted in the field, The charging chart may no longer apply.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the York 20 Series and is the answer not in the manual?

York 20 Series Specifications

General IconGeneral
BrandYork
Model20 Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals