Unitary Products Group 9
036-21311-003-A-0104
COOLING CAPACITIES - 3-1/2 TON (BHA042)
Temperature of Air on
Outdoor Coil
Air On Indoor Coil
1,050 CFM 1,225 CFM 1,400 CFM 1,575 CFM 1,750 CFM
WB°FWB°FWB°FWB°FWB°F
72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57
85 °F
Net Cap
MBH
39.6 36.8 33.1 30.6 43.3 40.3 36.2 33.4 46.9 43.7 39.2 36.3 47.7 44.4 39.9 36.8 48.4 45.1 40.5 37.4
Total Power
Input kW
4.15 4.05 3.98 4.01 4.17 4.07 4.00 4.03 4.19 4.09 4.02 4.05 4.33 4.22 4.14 4.18 4.46 4.35 4.27 4.30
Sensible Capacity
MBH
1
Entering Dry
Bulb,°F
86 24.9 30.8 33.1 30.6 28.4 35.0 36.2 33.4 31.9 39.3 39.2 36.3 34.4 42.2 39.9 36.8 37.0 45.1 40.5 37.4
83 21.9 27.8 32.7 30.6 24.9 31.5 36.0 33.4 27.8 35.2 39.2 36.3 29.8 37.6 39.9 36.8 31.8 40.0 40.5 37.4
80 18.9 24.8 29.7 28.9 21.3 28.0 33.5 32.6 23.8 31.1 37.3 36.3 25.1 33.0 38.9 36.8 26.5 34.8 40.5 37.4
77 15.9 21.8 26.7 25.9 17.8 24.4 30.0 29.0 19.7 27.0 33.2 32.2 20.5 28.3 34.3 32.2 21.3 29.6 35.3 32.2
74 12.9 18.8 23.8 22.9 14.3 20.9 26.5 25.5 15.6 23.0 29.2 28.1 15.9 23.7 29.6 27.5 16.1 24.3 30.1 27.0
71 - 15.8 20.8 19.9 - 17.3 22.9 22.0 - 18.9 25.1 24.0 - 19.0 25.0 22.9 - 19.1 24.9 21.8
68 - 12.8 17.8 16.9 - 13.8 19.4 18.4 - 14.8 21.0 19.9 - 14.4 20.3 18.2 - 13.9 19.6 16.5
95 °F
Net Cap
MBH
38.5 34.6 30.5 28.0 41.6 37.4 33.0 30.2 44.8 40.3 35.4 32.5 45.5 40.9 36.0 33.0 46.2 41.5 36.5 33.5
Total Power
Input kW
4.34 4.25 4.15 4.18 4.40 4.31 4.20 4.24 4.46 4.37 4.26 4.30 4.58 4.49 4.38 4.42 4.71 4.61 4.50 4.54
Sensible Capacity
MBH
1
Entering Dry
Bulb,°F
86 24.6 30.7 30.5 28.0 27.6 34.3 33.0 30.2 30.6 38.0 35.4 32.5 33.1 39.7 36.0 33.0 35.6 41.5 36.5 33.5
83 21.6 27.7 30.5 28.0 24.0 30.8 33.0 30.2 26.5 33.9 35.4 32.5 28.4 36.2 36.0 33.0 30.4 38.6 36.5 33.5
80 18.6 24.7 29.4 26.9 20.5 27.2 32.4 29.7 22.4 29.8 35.4 32.5 23.8 31.6 36.0 33.0 25.2 33.4 36.5 33.5
77 15.6 21.7 26.4 23.9 17.0 23.7 28.9 26.2 18.4 25.7 31.4 28.4 19.1 27.0 31.3 28.4 19.9 28.2 31.3 28.3
74 12.6 18.7 23.4 21.0 13.4 20.2 25.3 22.7 14.3 21.6 27.3 24.4 14.5 22.3 26.7 23.7 14.7 23.0 26.1 23.1
71 - 15.7 20.4 18.0 - 16.6 21.8 19.1 - 17.5 23.2 20.3 - 17.7 22.0 19.1 - 17.8 20.9 17.9
68 - 12.7 17.4 15.0 - 13.1 18.3 15.6 - 13.5 19.1 16.2 - 13.0 17.4 14.4 - 12.5 15.7 12.7
105 °F
Net Cap
MBH
35.6 31.0 27.9 25.3 38.4 33.5 30.1 27.3 41.2 35.9 32.3 29.3 41.7 36.4 32.7 29.7 42.3 36.9 33.1 30.1
Total Power
Input kW
4.62 4.50 4.42 4.46 4.68 4.56 4.47 4.51 4.74 4.61 4.53 4.57 4.87 4.74 4.66 4.70 5.01 4.88 4.79 4.83
Sensible Capacity
MBH
1
Entering Dry
Bulb,°F
86 23.4 29.0 27.9 25.3 26.5 31.9 30.1 27.3 29.6 34.8 32.3 29.3 32.0 35.8 32.7 29.7 34.4 36.9 33.1 30.1
83 20.4 26.0 27.9 25.3 23.0 29.2 30.1 27.3 25.5 32.3 32.3 29.3 27.3 33.9 32.7 29.7 29.2 35.5 33.1 30.1
80 17.4 23.0 26.3 23.9 19.4 25.6 29.3 26.6 21.4 28.2 32.3 29.3 22.7 29.9 32.7 29.7 24.0 31.6 33.1 30.1
77 14.4 20.0 23.3 20.9 15.9 22.1 25.8 23.1 17.3 24.2 28.2 25.2 18.0 25.3 28.1 25.1 18.7 26.4 27.9 24.9
74 11.5 17.0 20.3 17.9 12.3 18.6 22.2 19.5 13.2 20.1 24.1 21.1 13.4 20.6 23.4 20.4 13.5 21.2 22.7 19.7
71 - 14.1 17.4 14.9 - 15.0 18.7 16.0 - 16.0 20.0 17.1 - 16.0 18.8 15.8 - 16.0 17.5 14.5
68 - 11.1 14.4 11.9 - 11.5 15.1 12.5 - 11.9 15.9 13.0 - 11.3 14.1 11.1 - 10.8 12.3 9.2
115 °F
Net Cap
MBH
32.6 27.4 25.3 22.7 35.1 29.5 27.2 24.4 37.5 31.6 29.1 26.1 38.0 31.9 29.4 26.4 38.4 32.3 29.7 26.7
Total Power
Input kW
4.91 4.75 4.69 4.73 4.96 4.80 4.74 4.79 5.02 4.86 4.80 4.84 5.17 5.00 4.94 4.98 5.32 5.15 5.08 5.13
Sensible Capacity
MBH
1
Entering Dry
Bulb,°F
86 22.3 27.4 25.3 22.7 25.4 29.5 27.2 24.4 28.5 31.6 29.1 26.1 30.8 31.9 29.4 26.4 33.2 32.3 29.7 26.7
83 19.3 24.4 25.3 22.7 21.9 27.6 27.2 24.4 24.4 30.8 29.1 26.1 26.2 31.5 29.4 26.4 28.0 32.3 29.7 26.7
80 16.3 21.4 23.3 20.9 18.3 24.1 26.2 23.5 20.3 26.7 29.1 26.1 21.5 28.3 29.4 26.4 22.7 29.9 29.7 26.7
77 13.3 18.4 20.3 17.9 14.8 20.5 22.7 20.0 16.3 22.6 25.0 22.0 16.9 23.6 24.8 21.7 17.5 24.6 24.5 21.5
74 10.3 15.4 17.3 14.9 11.2 17.0 19.1 16.4 12.2 18.5 20.9 17.9 12.2 19.0 20.1 17.1 12.3 19.4 19.3 16.3
71 - 12.4 14.3 11.9 - 13.4 15.6 12.9 - 14.5 16.8 13.9 - 14.3 15.5 12.4 - 14.2 14.1 11.0
68 - 9.4 11.3 8.9 - 9.9 12.0 9.4 - 10.4 12.8 9.8 - 9.7 10.8 7.8 - 9.0 8.9 5.8
125 °F
Net Cap
MBH
29.7 23.8 22.7 20.0 31.8 25.5 24.3 21.5 33.9 27.2 25.9 22.9 34.2 27.4 26.1 23.1 34.5 27.7 26.3 23.3
Total Power
Input kW
5.2 5.0 5.0 5.0 5.2 5.1 5.0 5.1 5.3 5.1 5.1 5.1 5.5 5.3 5.2 5.3 5.6 5.4 5.4 5.4
Sensible Capacity
MBH
1
Entering Dry
Bulb,°F
86 21.1 25.7 22.7 20.0 24.3 27.1 24.3 21.5 27.5 28.4 25.9 22.9 29.7 28.0 26.1 23.1 32.0 27.7 26.3 23.3
83 18.1 22.7 22.7 20.0 20.8 26.0 24.3 21.5 23.4 29.3 25.9 22.9 25.1 29.2 26.1 23.1 26.7 29.1 26.3 23.3
80 15.2 19.8 20.3 17.9 17.2 22.5 23.1 20.4 19.3 25.2 25.9 22.9 20.4 26.6 26.1 23.1 21.5 28.1 26.3 23.3
77 12.2 16.8 17.3 14.9 13.7 18.9 19.6 16.9 15.2 21.1 21.8 18.8 15.8 22.0 21.5 18.4 16.3 22.9 21.1 18.0
74 9.2 13.8 14.3 11.9 10.2 15.4 16.0 13.3 11.1 17.0 17.8 14.7 11.1 17.3 16.8 13.8 11.1 17.6 15.9 12.8
71 - 10.8 11.3 8.9 - 11.8 12.5 9.8 - 12.9 13.7 10.7 - 12.7 12.2 9.1 - 12.4 10.7 7.6
68 - 7.8 8.3 5.9 - 8.3 8.9 6.2 - 8.8 9.6 6.6 - 8.0 7.5 4.5 - 7.2 5.5 2.4
1
= These capacities are net capacities - indoor fan heat deducted.
ALL SENSIBLE CAPACITY

Other manuals for York Champion Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the York Champion Series and is the answer not in the manual?

York Champion Series Specifications

General IconGeneral
BrandYork
ModelChampion Series
CategoryHeat Pump
LanguageEnglish

Related product manuals