8 Unitary Products Group
Note 1: Complete York ERV model number includes the electrical information. Example: DM180 needing 2800 CFM
outside of air at 230 volts/3 phase. Model would be a VR028A15H2AAA1.
Note 2: For VR074 and VR122 units used with an economizer must have the Start-Stop-Jog (SSJ) option.
TABLE 3: PERFORMANCE - 15 THROUGH 25 TON UNITS
Use this table to determine ventilation and size requirements. Table shows York packaged units and matching ERV model,
Air Flow Range, and ARI rated Net Effectiveness at 100% of rated CFM.
“R” Series Stationary Wheel for Units without Economizers
York
Packaged Unit
Model No.
Unit
Size
(Tons)
ERV CFM
Range
Matching ERV
Model
Voltage &
Phase
Voltage
Code
Nominal ARI Data (Total
CFM
Net Effectiveness
Heating Cooling
DM 180
DH 180
BP 180
15
1500-2200 VR028A15M
208/230v-3ph 2
1950 71% 70%460v-3ph 4
575v-3ph 5
2200-2800 VR028A15H
208/230v-3ph 2
2600 65% 63%460v-3ph 4
575v-3ph 5
2800-3600 VR036A15H
208/230v-3ph 2
3100 65% 63%460v-3ph 4
575v-3ph 5
3400-4600 VR046A15H
208/230v-3ph 2
3900 65% 63%460v-3ph 4
575v-3ph 5
4800-5600 VR062A15M
208/230v-3ph 2
4125 71% 70%460v-3ph 4
575v-3ph 5
5500-6200 VR062A15H
208/230v-3ph 2
5500 65% 63%460v-3ph 4
575v-3ph 5
DM 240
DM 300
DH 240
BP 240
BQ 240
DJ 180
DJ 210
DJ 240
DJ 300
DR 180
DR 240
DR 300
15 - 25
2200-2800 VR028A25H
208/230v-3ph 2
2600 65% 63%460v-3ph 4
575v-3ph 5
2800-3600 VR036A25H
208/230v-3ph 2
3100 65% 63%460v-3ph 4
575v-3ph 5
3400-4600 VR046A25H
208/230v-3ph 2
3900 65% 63%460v-3ph 4
575v-3ph 5
4800-5600 VR062A25M
208/230v-3ph 2
4125 71% 70%460v-3ph 4
575v-3ph 5
5500-6200 VR062A25H
208/230v-3ph 4
5500 65% 63%460v-3ph 5
575v-3ph 2
(See note 2)
(See
note 2)
6000-8000 VR074A40*
208/230v-3ph 2
6600 65% 63%460v-3ph 4
575v-3ph 5
8000-13000 VR122A40*
208/230v-3ph 2
10800 65% 63%460v-3ph 4
575v-3ph 5