SECTION 4 – INSTALLATION
FIGURE 10 - SINGLE-POINT SUPPLY CONNECTION – TERMINAL BLOCK, NON-FUSED DISCONNECT
SWITCH OR CIRCUIT BREAKER (0043 – 0066)
SINGLE-POINT SUPPLY CONNECTION – TERMINAL BLOCK, NON-FUSED
DISCONNECT SWITCH OR CIRCUIT BREAKER
It is possible that multiple sources of
power can be supplying the unit power
panel. To prevent serious injury or
death, the technician should verify
that NO LETHAL VOLTAGES are
present inside the panel AFTER dis-
connecting power, PRIOR to working
on equipment.
The unit evaporator heater uses
120VAC. Disconnecting 120VAC pow-
er from the unit, at or below freezing
temperatures, can result in damage to
the evaporator and unit as a result of
the chilled liquid freezing.
Electrical Notes and Legend located on Page 59.
LD07719
Power PanelControl Panel
Terminal Block,
NF Disconnect SW
or Circuit Breaker
1L11L2 1L3
GRD
MICROPANEL
2
L
CTB2
13 14
CTB1
Field Provided Unit Power Supply
Field Provided 120- 1-60
Micropanel Power Supply if Control
Transformer not Supplied
Flow Switch
See electrical note 9
Power PanelControl PanelPower PanelControl Panel
Terminal Block,
NF Disconnect SW
or Circuit Breaker
1L11L2 1L31L11L2 1L3
GRDGRDGRD
MICROPANEL
2
L
CTB2
2
L
CTB2
13 1413 14
CTB1
Field Provided Unit Power Supply
Field Provided 120- 1-60
Micropanel Power Supply if Control
Transformer not Supplied
Flow Switch
See electrical note 9