203
JOHNSON CONTROLS
FORM 150.67-NM1
ISSUE DATE: 4/28/2017
9
SYS 1 HGBP STATUS TB7-7 IS:
SYS 2 COMP 1 STATUS TB10-2 IS:
SYS 2 LLSV STATUS TB10-3 IS:
SYS 2 COMP 2 STATUS TB10-4 IS:
SYS 2 COMP 3 STATUS TB10-5 IS:
SYS 1 FAN OUTPUT 1 TB7-8 IS:
SYS 1 FAN OUTPUT 2 TB7-9 IS:
SYS 1 FAN OUTPUT 3 TB7-10 IS:
SYS 2 FAN OUTPUT 1 TB10-8 IS:
SYS 2 FAN OUTPUT 2 TB10-9 IS:
SYS 2 FAN OUTPUT 3 TB10-10 IS:
EVAP HEATER STATUS TB8-2 IS:
SYS 1 ALARM STATUS TB8-3 IS:
SYS 2 ALARM STATUS TB9-2 IS:
EVAP PUMP STATUS TB8-6,7 IS:
SYS 2 HGBV STATUS TB10-7 IS:
SPARE DO TB8-4 IS:
SPARE DO TB8-5 IS:
SPARE DO TB8-8, 9 IS:
SPARE DO TB9-4 IS:
SYS 1 EEV OUTPUT TB5-1, 2 = XXX%
SYS 2 EEV OUTPUT TB6-1, 2 = XXX%
SYS 1 COND FAN SPEED J15-1,5 = XXX%
SYS 2 COND FAN SPEED J15-2,6 = XXX%
SPARE AO J15-3,7 = XXX%
SPARE AO J15-4,8 = XXX%
DATA LOGGING MODE 1 = ON, 0 = OFF
DATA LOGGING TIMER X SECS
SOFT START (disabled)
REFRIGERANT TYPE (R410A only)
EXPANSION VALVE TYPE (Thermostatic Only)
REMOTE TEMP RESET OPTION =
REMOTE INPUT SERVICE TIME =
“NORTH AMERICAN FEATURE SET ENABLED”
HYDRO PUMP SELECTION
EVAP PUMP TOTAL RUN HOURS
SYS 1 HOURS
SYS 2 HOURS
SYS 1 STARTS
SYS 2 STARTS
Each display will also show the output connection on
the microboard for the respective output status shown.
For example:
S Y S 1 L L S V S T A T U S
T B 10 - 3 I S O F F
This display indicates that the system 1 liquid line sole-
noid valve is OFF, and the output connection from the
microboard is coming from terminal block 10 – pin 3.
SECTION 9 – SERVICE AND TROUBLESHOOTING
CLEARING HISTORY BUFFERS
The history buffers may be cleared by pressing the
HISTORY key and then repeatedly pressing the UP
arrow key until you scroll past the last history buffer
choice. The following message will be displayed:
I I N I T I A L I Z E H I S T O R Y
E N T E R = Y E S
Pressing the ENTER/ADV key at this display will
cause the history buffers to be cleared. Pressing any
other key will cancel the operation.
DO NOT CLEAR BUFFERS. Impor-
tant information may be lost. Contact
factory service.
SERVICE MODE
Service Mode is a mode that allows the user to enable
or disable all of the outputs (except compressors) on
the unit, change chiller configuration setup parameters
and view all the inputs to the microboard.
To enter Service Mode, turn the Unit Switch OFF and
press the following keys in the sequence shown; PRO-
GRAM, UP ARROW, UP ARROW, DOWN ARROW,
DOWN ARROW, ENTER. Service Mode will time out
after 30 minutes and return to normal control mode, if
the panel is accidentally left in this mode. Otherwise,
turning the Unit Switch ON will take the panel out of
Service Mode.
SERVICE MODE – OUTPUTS
After pressing the key sequence as described, the con-
trol will enter Service Mode permitting the outputs
(except compressors), operating hours, refrigerant
type, expansion valve type, and start/hour counters to
be viewed and or modified. The ENTER/ADV key is
usedtoadvancethroughtheoutputs.Usingthe↑and↓
(UP/DOWN ) arrow keys will turn the respective digi-
tal output ON/OFF or modify the value.
Following is the order of outputs that will appear as the
ENTER/ADV key is pressed:
SYS 1 COMP 1 STATUS TB7-2 IS:
SYS 1 LLSV STATUS TB7-3 IS:
SYS 1 COMP 2 STATUS TB7-4 IS:
SYS 1 COMP 3 STATUS TB7-5 IS:

Table of Contents

Other manuals for York YCAL0046

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the York YCAL0046 and is the answer not in the manual?

York YCAL0046 Specifications

General IconGeneral
BrandYork
ModelYCAL0046
CategoryChiller
LanguageEnglish

Related product manuals