SECTION 9 – SERVICE AND TROUBLESHOOTING
TROUBLESHOOTING (CONT’D)
TABLE 37 - TROUBLESHOOTING
PROBLEM CAUSE SOLUTION
LACK OF COOLING EFFECT
1. Fouled evaporator surface. Low
suction pressure will be observed.
1. Contact the local Johnson
Controls Service representative.
2. Improper ow through the evaporator. 2. Reduce ow to within chiller
design specs. See Limitations in
Installation section.
3. Low refrigerant charge. Low suction
pressure will be observed.
3. Check subcooling and add
charge as needed.