Physical data, heat pump units
Characteristics YCSA-H 120 T and TP YCSA-H150 T and TP
Cooling capacity kW 114 145
Heating capacity kW 119.6 150
Capacity control % 25/50/75/100%
Power supply V/ph 400.3.50
Compressor consumption in cooling kW 4 x 10.2 4 x 11.8
Compressor consumption in heating kW 4 x 9.25 4 x 12.5
Compressor amperage in cooling A 4 x 18.2 4 x 21.4
Compressor amperage in heating A 4 x 16.9 4 x 21.6
No. of refrigerant circuits 2
No. of compressors 2 TANDEM
Compressor type SCROLL
Oil charge in litres l 4 x 3.25 4 x 4.14
Oil type POLYOL ESTER OIL
Heat exchanger PLATES
Nominal flow in cooling l/h 19 610 24 940
Minimum water volume of the inst. l 445 565
No. of fans 4
Fan diameter mm 630 710
Total fan consumption W 4 x 600 4 x 860
Total fan amperage A 4 x 2.75 4 x 3.9
Total air flow m
3
/h 36 000 48 000
Refrigerant type R-410A
Refrigerant charge kg 2 x 20 2 x 29
Sound power level dB (A) 86 88
Sound power level at 5 m. dB (A) 64 66
Sound power level at 10 m. dB (A) 58 60
Sound power level LN dB (A) 82 84
Sound power level at 5 m. LN dB (A) 60 62
Sound power level at 10 m. LN dB (A) 54 56
Dimensions
Length mm 3 416 3 770
Width mm 1 101
Height mm 2 190 2 263
Water connections, socket 2 1/2"