SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION
JOHNSON CONTROLS
85
FORM 160.87-OM1
ISSUE DATE: 8/24/2018
2
OVERVIEW
This screen displays all information pertaining to the
Economizer Solid State Starter.
DISPLAY ONLY
Motor Run (LED)
Indicates whether the digital output from the controls is
commanding the motor to RUN.
Motor Heater (LED)
Indicates whether the optional Motor Heater is ON or
OFF. Displayed if optional Motor Heater is installed.
Motor Current % Full Load Amps
Displays the motor current as a percentage of the Full
Load Amps (FLA) value.
Override Threshold Setpoint
Displays the current limit in use. This value could
come from a 0 to 20mA, 4 to 20mA, 0 to 10VDC or 2
to 10VDC input in Analog Remote mode, PWM signal
in Digital Remote mode, SC-EQ communication card
in ISN (BAS) Remote mode or a locally programmed
value in Local mode.
Pulldown Demand Time Left
Displays the time remaining in the programmed
pulldown period.
Input Power
Displays the kilowatts measured by the Solid State
Starter.
KW Hours
Displays the cumulative amount of kilowatts used over
time.
Starter Model
Displays the Solid State Starter model that is applied
to the chiller. Starter Models are 7L, 14L, 26L or 33L.
Voltage – Phase A, B, C
Displays the 3-phase input line voltage measured by
the Solid State Starter.
Current – Phase A, B, C
Displays the 3-phase motor current values measured
by the Solid State Starter.
ECONOMIZER SOLID STATE STARTER SCREEN
LD22050
FIGURE 35 - ECONOMIZER SOLID STATE STARTER SCREEN