EasyManuals Logo

York YLAA0101 User Manual

York YLAA0101
206 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #177 background imageLoading...
Page #177 background image
JOHNSON CONTROLS
177
SECTION 8 UNIT OPERATION
FORM 150.72-ICOM6
ISSUE DATE: 08/03/2022
8
TABLE 24 - SAMPLE COMPRESSOR STAGING FOR RETURN WATER CONTROL
4 COMPRESSOR
COOLING SETPOINT = 45 °F (7.2 °C) RANGE = 10 °F (5.6 °C)
# OF COMP ON 0 * 1+HG 1 2 3 4
RWT
45°F
(7.2°C)
46.25°F
(7.9°C)
47.5°F
(8.6°C)
50.0°F
(10.0°C)
52.5°F
(11.4°C)
55.0°F
(12.8°C)
*Unloading only
0 1 2 3 4 5
6
LAST RUN TIME OF LEAD SYSTEM (MINUTES)
SETPOINT
ADJUST (DEG. F)
6
5
4
3
2
1
0
FIGURE 47 - SETPOINT ADJUST
LD11415
LEAVING CHILLED LIQUID CONTROL
OVERRIDE TO REDUCE CYCLING
To avoid compressor cycling the microprocessor ad-
justs the setpoint upward temporarily. The last run time
of the system is saved. If the last run time was greater
than 5 minutes, do not take any action. If the last run
time for the lead system was less than 5 minutes, the
microprocessor increases the setpoint high limit ac-
cording to the chart at right, with a maximum value
allowed of 50°F. See Figure 47.
If adding the setpoint adjust value to the setpoint high
limit causes the setpoint high limit to be greater than
50°F, the setpoint high limit is set to 50°F and the dif-
ference is added to the setpoint low limit.
When a system runs for greater than 5 minutes, the set-
point adjust sets back to 0. This occurs while the sys-
tem is still running.

Table of Contents

Other manuals for York YLAA0101

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the York YLAA0101 and is the answer not in the manual?

York YLAA0101 Specifications

General IconGeneral
BrandYork
ModelYLAA0101
CategoryChiller
LanguageEnglish

Related product manuals