OPERATIONAL LIMITATIONS
TABLE 4 - TEMPERATURES AND FLOWS
UNIT
DESIGNATION
TEMPERATURE, °F (°C) WATER FLOW, GPM (L/S) AIR ON CONDENSER, °F (°C)
MINIMUM MAXIMUM NOMINAL MINIMUM MAXIMUM MINIMUM MAXIMUM
STANDARD EFFICIENCY
YLAA0070SE 40 (4.4) 55 (12.8) 170 (10.7) 60 (3.8) 285 (18.0) -10 (-23.3) 125 (51.7)
YLAA0080SE 40 (4.4) 55 (12.8) 186 (11.7) 100 (6.3) 355 (22.4) -10 (-23.3) 125 (51.7)
YLAA0089SE 40 (4.4) 55 (12.8) 205 (12.9) 100 (6.3) 385 (24.3) -10 (-23.3) 125 (51.7)
YLAA0100SE 40 (4.4) 55 (12.8) 230 (14.5) 100 (6.3) 385 (24.3) -10 (-23.3) 125 (51.7)
YLAA0120SE 40 (4.4) 55 (12.8) 286 (18.0) 150 (9.5) 625 (39.4) -10 (-23.3) 125 (51.7)
YLAA0136SE 40 (4.4) 55 (12.8) 299 (18.9) 150 (9.5) 625 (39.4) -10 (-23.3) 125 (51.7)
YLAA0155SE 40 (4.4) 55 (12.8) 347 (21.9) 150 (9.5) 625 (39.4) -10 (-23.3) 125 (51.7)
YLAA0170SE 40 (4.4) 55 (12.8) 406 (25.6) 150 (9.5) 625 (39.4) -10 (-23.3) 125 (51.7)
HIGH EFFICIENCY
YLAA0041HE 40 (4.4) 55 (12.8) 94 (5.9) 41 (2.6) 224 (14.1) -10 (-23.3) 125 (51.7)
YLAA0048HE 40 (4.4) 55 (12.8) 117 (7.4) 48 (3.0) 224 (14.1) -10 (-23.3) 125 (51.7)
YLAA0058HE 40 (4.4) 55 (12.8) 136 (8.6) 60 (3.8) 285 (18.0) -10 (-23.3) 125 (51.7)
YLAA0065HE 40 (4.4) 55 (12.8) 149 (9.4) 60 (3.8) 285 (18.0) -10 (-23.3) 125 (51.7)
YLAA0081HE 40 (4.4) 55 (12.8) 186 (11.7) 150 (9.5) 625 (39.4) -10 (-23.3) 125 (51.7)
YLAA0082HE 40 (4.4) 55 (12.8) 186 (11.7) 100 (6.3) 385 (24.3) -10 (-23.3) 125 (51.7)
YLAA0092HE 40 (4.4) 55 (12.8) 205 (12.9) 100 (6.3) 385 (24.3) -10 (-23.3) 125 (51.7)
YLAA0101HE 40 (4.4) 55 (12.8) 237 (15.0) 100 (6.3) 385 (24.3) -10 (-23.3) 125 (51.7)
YLAA0125HE 40 (4.4) 55 (12.8) 282 (17.8) 100 (6.3) 385 (24.3) -10 (-23.3) 125 (51.7)
YLAA0139HE 40 (4.4) 55 (12.8) 302 (19.1) 150 (9.5) 625 (39.4) -10 (-23.3) 125 (51.7)
YLAA0142HE 40 (4.4) 55 (12.8) 310 (19.6) 150 (9.5) 625 (39.4) -10 (-23.3) 125 (51.7)
YLAA0156HE 40 (4.4) 55 (12.8) 351 (22.1) 150 (9.5) 625 (39.4) -10 (-23.3) 125 (51.7)
YLAA0175HE 40 (4.4) 55 (12.8) 419 (26.4) 150 (9.5) 625 (39.4) -10 (-23.3) 125 (51.7)
YLAA0200HE 40 (4.4) 55 (12.8) 467 (29.5) 230 (14.5) 625 (39.4) -10 (-23.3) 125 (51.7)
YLAA0230HE 40 (4.4) 55 (12.8) 529 (33.4) 230 (14.5) 650 (41.0) -10 (-23.3) 125 (51.7)
NOTES:
1. For leaving liquid temperature below 40°F (4.4°C) (to 10°F [-12.2°C]), an optional low temperature glycol kit is required. Contact your
nearest Johnson Controls O󰀩ce for application requirements.
2. For leaving liquid temperature higher than 55°F (12.8°C), contact the nearest Johnson Controls O󰀩ce for application guidelines.
3. The evaporator is protected against freezing to -20°F (-28.9°C) with an electric heater as standard.
4. For operation at temperatures below 30°F (-1.1°C), install the optional Low Ambient Kit on the system.
5. For operation at temperatures below 0°F (-17.8°C), install the optional Low Ambient Kit with Variable Speed Fans on the system.
Excessive ow will cause damage to the
cooler. Do not exceed the maximum cooler
ow. Special care should be taken when
multiple chillers are fed by a single pump.
SECTION 5 TECHNICAL DATA

Table of Contents

Other manuals for York YLAA0101

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the York YLAA0101 and is the answer not in the manual?

York YLAA0101 Specifications

General IconGeneral
BrandYork
ModelYLAA0101
CategoryChiller
LanguageEnglish

Related product manuals