Technical data 47
7. Technical data
Ratings
Note: When choke is not used, input current is effected by supply network and
impedance.
Use the table in Fuses and alternate short-circuit protection (page 50) to correctly
size the input cabling as well as input fuses or MMP for branch circuit protection.
Sizing will be determined by the actual input current which is dependent on the input
line voltage and the input choke selection and rated motor current. If motor rated
current is below I
2N
, I
1N
is reduced relatively.
Type code Input Output Frame
size
without choke
or reactor
with choke or
5% reactor
ACS320- I
1N
I
1N
(480 V)
I
1N
I
1N
(480 V)
I
LD
2)
I
2N
I
2max
3)
P
N
x = E/U
1)
A A A A A A A kW hp
1-phase supply voltage 200…240 V units (Confirm output ratings meet motor requirements)
01x-02A4-2 6.1 - 4.5 - 2.3 2.4 4.0 0.37 0.5 R0
01x-04A7-2 11.4 - 8.1 - 4.5 4.7 7.9 0.75 1 R1
01x-06A7-2 16.1 - 11.0 - 6.5 6.7 11.4 1.1 1.5 R1
01x-07A5-2 16.8 - 12.0 - 7.2 7.5 12.6 1.5 2 R2
01x-09A8-2 21.0 - 15.0 - 9.4 9.8 16.5 2.2 3 R2
3-phase supply voltage 200…240 V units
03x-02A6-2 4.7 - 2.6 - 2.4 2.6 4.2 0.37 0.5 R0
03x-03A9-2 6.7 - 3.9 - 3.5 3.9 6.1 0.55 0.75 R0
03x-05A2-2 8.4 - 5.2 - 4.7 5.2 8.2 0.75 1 R1
03x-07A4-2 13.0 - 7.4 - 6.7 7.4 11.7 1.1 1.5 R1
03x-08A3-2 13.2 - 8.3 - 7.5 8.3 13.1 1.5 2 R1
03x-10A8-2 15.7 - 10.8 - 9.8 10.8 17.2 2.2 3 R2
03x-14A6-2 23.9 - 14.6 - 13.3 14.6 23.3 3 3 R2
03x-19A4-2 27.3 - 19.4 - 17.6 19.4 30.8 4 5 R2
03x-26A8-2 45.0 - 26.8 - 24.4 26.8 42.7 5.5 7.5 R3
03x-34A1-2 55.0 - 34.1 - 31.0 34.1 54.3 7.5 10 R4
03x-50A8-2 76.0 - 50.8 - 46.2 50.8 80.9 11.0 15 R4
3-phase supply voltage 380…480 V units
03x-01A2-4 2.4 2.0 1.3 1.1 1.1 1.2 2.1 0.37 0.5 R0
03x-01A9-4 4.0 3.3 2.0 1.7 1.7 1.9 3.3 0.55 0.75 R0
03x-02A4-4 4.5 3.8 2.5 2.1 2.2 2.4 4.2 0.75 1.0 R1
03x-03A3-4 6.6 5.5 3.5 2.9 3.0 3.3 5.8 1.1 1.5 R1