IP20Protection degree
Pollution degree 2 & meas. / overvoltage cat. IIInstallation in
Mechanical specifications
109 × 23.5 × 104 mmWithout 4501Dimensions (Height ×
Width × Depth)
109 × 23.5 × 116 mmWith 4501
approximately 185 gWeight
approximately 200 gWeight including 4501
0.13 … 2.08 mm
2
(AWG 26 … 14) stranded wireWire sizeTerminals
0.5 N·m (4.4 lbf·in)Tightening torque
±1 mm2 … 13.2 HzVibration
±0.7 g13.2 … 100 Hz
Approvals
• ATEX Ex II (1) G D
• IECEx
• EAC Ex
• SIL 2 certified according to IEC 61508
For the complete list of approvals, see the relay data sheet.
Isolation data
2.6 kV AC / 300 V AC reinforced isolationTest/working: Input to anyIsolation voltage
2.6 kV AC / 300 V AC reinforced isolationAnalog output to supply
1.5 kV AC / 150 V AC reinforced isolationStatus relay to supply
For the complete relay technical data, see www.prelectronics.com.
General rules, notes and definitions
■ Validation of the safety functions
You must do an acceptance test (validation) to validate the correct operation of safety
functions.
Competence
The acceptance test of the safety function must be carried out by a competent person with
expertise and knowledge of the safety function as well as functional safety, as required by
IEC 61508-1 clause 6, and ATEX/Ex regulations. The test procedures and report must be
documented and signed by this person.
Validation procedure
You must do the acceptance test using the checklist given in section Start-up and acceptance
test:
• at initial start-up of the safety function
• after any changes related to the safety function (wiring, components,
safety-function-related parameter settings, etc.)
• after any maintenance work related to the safety function.
The acceptance test must include at least the following steps:
• you must have an acceptance test plan
• you must test all commissioned functions for proper operation, from each operation
location
62 Technical data