yes, up to 300 V AC
Supply circuit / Measuring
circuit
1)
Protective separation
(IEC/EN 61140, EN 50178)
yesSupply circuit / Output
circuits
yes
Measuring circuit
1)
/
Output circuits
noOutput circuit 1 / Output
circuit 2
3Pollution degree
IIIOvervoltage category
1)
Potential of measuring circuit = Potential of control circuit
For the complete relay technical data, see the CM-MSS.41 data sheet (2CDC112216D0201
[English]), available at library.abb.com.
■ DOLD MK 9163N.12/110-ATEX
Ordering information
0056901Part number
Power supply A1-A2
24 V AC/DCRated voltage
AC 0.8 … 1.1 UVoltage range
DC 0.9 … 1.25 U
H
at 10% residual ripple
DC 0.8 … 1.1 U
H
at 48% residual ripple
1.5 VAACNominal consumption
0.85 WDC
50 / 60 HzNominal frequency
45 … 65 HzFrequency range
20 msMax. bridging time on failure of aux. supply
< 40 msOperate delay
< 100 msRelease delay
Measuring circuit P1-P2
3.2 … 3.8 kohmResponse value
1.5 … 1.8 kohmRelease value
> 3.8 kohmBroken wire detection
< 20 ohmShort-circuit on measuring circuit
< 5 mW (R = 1.5 kohm)Loading of measuring circuit
≤ 2 V (R = 1.5 kohm)Measuring voltage
2 × 550 m4 mm
2
Maximum wire length
2 × 250 m2.5 mm
2
2 × 150 m1.5 mm
2
2 × 50 m0.5 mm
2
Reset circuit X1-X2
External remote reset X1-X2 with NO contact (voltage
free)
Function
Technical data 57