EasyManuals Logo
Home>ABB>Control Unit>NPBA-12

ABB NPBA-12 User Manual

ABB NPBA-12
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #39 background imageLoading...
Page #39 background image
NPBA-12 Installation and Start-up Guide A-1
Appendix A PROFIBUS Parameters
The table below shows the PROFIBUS Profile-specific Parameters. All
these values are of the unsigned16 data type.
PROFIBUS
Par. No.
Parameter Name R/W Description
918 NODE ADDRESS R Node address of the device
Allowable values: 2, ..., 126
947 FAULT NUMBER R The last fault occurred in the drive
0h = No fault
1000h = Generic fault
963 CURRENT BAUD RATE R Detected baud rate
0 = 12 Mbit/s
1 = 6 Mbit/s
2 = 3 Mbit/s
3 = 1.5 Mbit/s
4 = 500 kbit/s
5 = 187.5 kbit/s
6 = 93.75 kbit/s
7 = 45.45 kbit/s
8 = 19.2 kbit/s
9 = 9.6 kbit/s
255 = Invalid baud rate
964 DEVICE IDENTIFICATION R Identification number of this device (6012h)
965 PROFILE NUMBER R Profile number of this device (0302h)
967 CONTROL WORD R 16-bit word for controlling the drive
968 STATUS WORD R 16-bit word indicating drive status
971 STORE R/W 0 = No action
1 = Save drive parameters to non-volatile memory

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB NPBA-12 and is the answer not in the manual?

ABB NPBA-12 Specifications

General IconGeneral
BrandABB
ModelNPBA-12
CategoryControl Unit
LanguageEnglish

Related product manuals