6 Commissioning / Operation
6.1 Note on safety at work
This switchgear may only be operated by
specially trained personnel who are familiar with
the characteristics of the particular device.
Observe the relevant instructions in section 1.2.
6.2 Preparatory activities
(Prior to application of primary voltage)
Check the circuit-breaker for any kind of damage
or other injurious environmental influence, and
restore to the proper condition where necessary.
Remove any contamination, particularly on
insulating parts, which has occurred during
transit, storage or installation.
Check the primary and secondary connections
and the protectiv conductor terminal.
Charge the spring energy store by hand (see
section 6.3.1).
Perform a trial opening or closing operation of
the circuit-breaker using push-button 2 or 3
(taking into account any required supply voltage
and any relevant interlocks).
Check the charging motor on circuit-breakers
with motor-operated mechanisms by applying
supply voltage.
Remove the transport caps 11 from the poles.
They are marked accordingly.
Ensure that the Instruction Manual is available to
the operators at all times.
Remove the lifting lugs 1.3 for hoists (Figures 2/5,
2/6 and 6/2).
6.3 Operation of the circuit-breaker
(Figures 3/1 and 6/1)
6.3.1 Charging the spring energy store
Circuit-breakers with charging motors:
Charging takes place automatically.
If the charging motor breaks down, the charg-
ing process can be carried out or completed
manually.
Circuit-breakers with manual charging mecha-
nisms:
Insert charging lever 9 into recess 6 and
pump up and down for approx. 25 strokes
until the charged condition is displayed.
When the charged condition is reached, the
charging mechanism automatically disengages,
and further strokes of the charging lever have no
effect.
Key to the charging condition indications:
Discharged Charged
As a precondition for an auto-reclosing
sequence, the operating mechanism is either
(re-)charged after a closing operation
automatically by the charging motor, or it
requires (re-)charging by hand if the operating
mechanism is of the manual type.
6.3.2 Closing and opening
Closing:
Press mechanical ON push-button 2, or
operate the electrical control unit.
Opening:
Press mechanical OFF push-button 3, or
operate the electrical control unit.
Observe the notes in section 3.2.1.
The operating cycle counter 5 is automatically
incremented by one complete figure with
each switching cycle. On completion of a
switching operation the position indicator 4
in the window of front plate 1.1 shows the
appropriate position of the circuit-breaker.
Anti-pumping relay:
The anti-pumping relay -K0 (wiring diagram in
figure 7/5) prevents repeated ON-OFF swit-
ching operations if, for example, the breaker
is tripped by a protection relay in response to
a primary side fault while a permanent
electrical closing command is simultaneously
applied. The circuit-breaker can then only be
closed after the closing command has been
interrupted.
Closing on failure of supply voltage:
With standard equipment:
On failure of the control voltage, mechanical
closing by means of ON push-button 2 is
possible at any time.
With blocking magnet -Y1 fitted:
On failure of the control voltage, blocking
magnet -Y1 mechanically locks the ON
haflshaft and simultaneously interrupts the
circuit shunt release ON -Y3 via the cor-
responding auxiliary switch -S2.
Closing with the blocking magnet de-
energised requires manipulation of the
circuit-breaker operating mechanism:
Remove front plate 1.1.
Take care to avoid rotating parts!
Opening on failure of supply voltage:
On failure of the supply voltage, mechanical
opening by means of OFF push-button 3 is
possible at any time.

Table of Contents

Other manuals for ABB VD4 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB VD4 Series and is the answer not in the manual?

ABB VD4 Series Specifications

General IconGeneral
BrandABB
ModelVD4 Series
CategoryCircuit breakers
LanguageEnglish

Related product manuals