7
2.2 Technical data
Releases and blocking magnet
Equipment Power consumption
1)
AC DC
VA W
Shunt release OFF -Y2
3)
, -Y9
3)
250 250
-Y2
5)
, -Y9
5)
310 310
Shunt release ON -Y3
3)
250 250
-Y3
5)
310 310
Blocking magnet -Y1
3) 5)
10 10
Undervoltage release: -Y4
• undelayed
3) 5)
11 10
• delayed
4)
10 –
Indirect overcurrent release with intermediate current transformer: -Y7
• two-phase 3.5
2)
/15 –
• three-phase 2.0
2)
/15 –
1)
Approximate values
2)
With short-circuited intermediate current transformer
3)
Rated supply voltages AC: 110 and 220 V, DC: 24, 48, 60, 110
and 220 V
4)
See RN3U for supply voltage
5)
Rated supply voltage AC: 240 V, DC: 125 and 240 V
6)
At rated supply voltage
7)
With rated short-circuit breaking current 63 kA
2.3 Technical data
Motor-operated mechanisms
Groschopp-Motor
Rated Power Motor protection Charging
supply consumpt- (ABB-Stotz m.c.b.) time
voltage ion
1)
(maxi-
mum)
6)
V VA/W A s
AC
110 260 1.6 S 281UC-K 10
220 260 0.75 10
240 260 0.75 10
DC
60 240 3.0 S 282UC-K 10
110 230 1.6 10
125 260 1.6 10
220 240 0.75 10
240 260 0.75 10
Gefeg-Motor
7)
Rated Power Motor protection Charging
supply consumpt- (ABB-Stotz m.c.b.) time
voltage ion
1)
(maxi-
mum)
6)
V VA/W A s
AC
110 150 1.6 S 281UC-K 15
220 150 0.75 15
240 170 0.75 15
DC
24 130 4.0 S 282UC-K 15
48 130 3.0 15
60 130 2.0 15
110 140 1.0 15
125 160 1.0 15
220 140 0.75 15
240 150 0.75 15