9 Application of the X-ray regulations
One of the physical properties of vacuum insulation
is the possibility of X-ray emissions when the con-
tact gap is open. The specified test performed by
the Physikalisch-Technische Bundesanstalt (PTB)
in Braunschweig demonstrates that the local dos-
age output of 1 µSv/h at a distance of 10 cm from
the touchable surface is not exceeded when the
rated voltage is applied.
The results are as follows:
Testing of the switching device or the vacuum
interrupter to VDE 0671 part 100 or IEC 62271-
100 at the relevant rated power frequency
withstand voltage may only be performed by
trained personnel observing the stipulations of the
EU basic standard (Stipulation 96/29/Euratom
of the senate from 13 May 1996 (ABI.L 159 from
29 June 1996)).
Application of the rated power frequency with-
stand voltage specified for the switching device
by VDE 0671 part 100 or IEC 62271-100 is
completely safe.
Higher voltages than the rated power frequency
withstand voltage or DC test voltage specified in
VDE or IEC standards must not be applied!
The containment of the above mentioned local
dosage output with the vacuum interrupter in the
open position is dependent on maintenance of
the specified distance between the contacts
(which is automatically ensured with correct
mechanism function and force transmission).
Safety clearances must be maintained.

Table of Contents

Other manuals for ABB VD4

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB VD4 and is the answer not in the manual?

ABB VD4 Specifications

General IconGeneral
TypeVacuum Circuit Breaker
Rated VoltageUp to 36 kV
Rated Short-Circuit Breaking CurrentUp to 63 kA
Frequency50/60 Hz
StandardsIEC 62271-100
ApplicationMedium voltage power distribution
Rated Short-Time Withstand CurrentUp to 63 kA for 3 seconds
Mechanical LifeUp to 30, 000 operations
InstallationFixed / Withdrawable
Operating MechanismSpring-operated
Rated Current630 A / 800 A / 1250 A / 1600 A / 2000 A / 2500 A / 3150 A / 4000 A
Electrical LifeUp to 10, 000 operations at rated current
Control Voltage24 V DC, 48 V DC, 110 V DC, 220 V DC, 110 V AC, 230 V AC

Related product manuals