7
Rated voltage kV 12 17.5 24
Rated frequency Hz 50/60 50/60 50/60
Rated lightning impulse withstand voltage kV 75 95 125
Rated power frequency withstand voltage kV 28
1)
38
1)
50
Rate of rise of transient recovery voltage kV/µs 0.34 0.42 0.47
Peak of transient recovery voltage kV 20.6 30 41
Rated operating sequence O-3 min-CO-3 min-CO
Rated operating sequence with autoreclosing O-0.3 s-CO-3 min-CO
1)
At the rated supply voltage.
2)
If the activating relay contact cannot itself interrupt the release
coil current.
Guideline values for function times:
Closing time approx. 60 ms
Opening time 45 ms
Arcing time (at 50 Hz) 15 ms
Break time 60 ms
Minimum command
time on closing 20 ms
1)
(120 ms
2)
)
Minimum command
time on opening 20 ms
1)
( 80 ms
2)
)
2.2 Technical data
Releases and blocking magnet
Equipment Power consumption
1)
AC DC
VA W
Shunt release OFF -Y2
3)
, -Y9
3)
250 250
-Y2
5)
, -Y9
5)
310 310
Shunt release ON -Y3
3)
250 250
-Y3
5)
310 310
Blocking magnet -Y1
3) 5)
10 10
Undervoltage release: -Y4
• undelayed
3) 5)
11 10
• delayed
4)
10
Indirect overcurrent release -Y7
with intermediate current transformer:
• two-phase 3.5
2)
/15
• three-phase 2.0
2)
/15
1)
Approximate values
2)
With short-circuited intermediate current transformer
3)
Rated supply voltages AC: 110 and 220 V, DC: 24, 48, 60, 110 and 220 V.
4)
See RN3U for supply voltage
5)
Rated supply voltage AC: 240 V, DC: 125 and 240 V.
1)
42 kV on request.