22 Rockwell Automation Publication CNET-IN005A-EN-P - May 2011
Chapter 2 Install a 1768 ControlNet Communication Module
Redundant Media
The 1768-CNBR bridge module has two ControlNet ports to support
redundant media. For information about using the module with redundant
media, refer to Chapter 3
.
North American Hazardous Location Approval
The following information applies when operating this equipment
in hazardous locations.
Informations sur l’utilisation de cet équipement en environnements
dangereux.
Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I
Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous
locations only. Each product is supplied with markings on the rating
nameplate indicating the hazardous location temperature code. When
combining products within a system, the most adverse temperature code
(lowest "T" number) may be used to help determine the overall temperature
code of the system. Combinations of equipment in your system are subject
to investigation by the local Authority Having Jurisdiction at the time of
installation.
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu'à une
utilisation en environnements de Classe I Division 2 Groupes A, B, C, D
dangereux et non dangereux. Chaque produit est livré avec des marquages
sur sa plaque d'identification qui indiquent le code de température pour les
environnements dangereux. Lorsque plusieurs produits sont combinés dans
un système, le code de température le plus défavorable (code de
température le plus faible) peut être utilisé pour déterminer le code de
température global du système. Les combinaisons d'équipements dans le
système sont sujettes à inspection par les autorités locales qualifiées au
moment de l'installation.
WARNING: EXPLOSION HAZARD
Do not disconnect equipment unless power
has been removed or the area is known to be
nonhazardous.
Do not disconnect connections to this
equipment unless power has been removed
or the area is known to be nonhazardous.
Secure any external connections that mate
to this equipment by using screws, sliding
latches, threaded connectors, or other
means provided with this product.
Substitution of components may impair
suitability for Class I, Division 2.
If this product contains batteries, they must
only be changed in an area known to be
nonhazardous.
WARNING: RISQUE D’EXPLOSION
Couper le courant ou s'assurer que
l'environnement est classé non dangereux
avant de débrancher l'équipement.
Couper le courant ou s'assurer que
l'environnement est classé non dangereux
avant de débrancher les connecteurs. Fixer
tous les connecteurs externes reliés à cet
équipement à l'aide de vis, loquets
coulissants, connecteurs filetés ou autres
moyens fournis avec ce produit.
La substitution de composants peut rendre
cet équipement inadapté à une utilisation en
environnement de Classe I, Division 2.
S'assurer que l'environnement est classé
non dangereux avant de changer les piles.
ATTENTION: Prevent Electrostatic Discharge
This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation.
Follow these guidelines when you handle this equipment:
Touch a grounded object to discharge potential static.
Wear an approved grounding wriststrap.
Do not touch connectors or pins on component boards.
Do not touch circuit components inside the equipment.
Use a static-safe workstation, if available.
Store the equipment in appropriate static-safe packaging when not in use.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley 1756-CNBR/E and is the answer not in the manual?

Allen-Bradley 1756-CNBR/E Specifications

General IconGeneral
BrandAllen-Bradley
Model1756-CNBR/E
CategoryController
LanguageEnglish

Related product manuals